name: neqsim-flow-accelerated-corrosion
version: "1.0.0"
description: "Flow-accelerated corrosion (FAC) and high-temperature pH in closed heating- and cooling-medium loops — magnetite film stability, mass-transfer-controlled wall thinning at bends and welds, wall shear stress, in-situ pH at operating temperature versus laboratory pH, alkaline margin above neutrality, and Cr-Mo material upgrade screening. USE WHEN: a task involves localised wall thinning or leaks at bends, elbows or circumferential welds in carbon-steel tubing; a closed glycol/water or water heating-medium, cooling-medium, boiler-feedwater or condensate loop; a WHRU, steam generator or economiser tube bundle; pH control of an amine-buffered loop; or any question of the form 'is the fluid alkaline enough at operating temperature?'. Anchors on neqsim.process.corrosion."
last_verified: "2026-08-07"
requires:
java_packages: [neqsim.process.corrosion, neqsim.process.chemistry.rca]
---
# NeqSim Flow-Accelerated Corrosion and High-Temperature pH Skill
Screening for **flow-accelerated corrosion (FAC)** — dissolution of the protective
magnetite film under mass-transfer control — and for the **in-situ pH** that
governs it.
## When this skill applies
- Localised wall thinning or leaks at **bends, elbows or circumferential welds**
in carbon-steel tube bundles, with intact surfaces nearby.
- Closed **heating- or cooling-medium loops** (glycol/water or water),
boiler-feedwater, condensate, WHRU / economiser / steam-generator tubes.
- Operating temperature roughly **90–250 °C**, peaking near 150 °C.
- Questions about **pH control** of an amine-buffered loop, or whether measured
chemistry is adequate.
## Two mistakes to avoid before anything else
**1. Do not judge a hot system by its laboratory pH.**
Laboratory pH is measured on a cooled sample, typically at 20–25 °C. Corrosion
happens at 150 °C. Two things move, by different amounts:
- The amine pK$_a$ falls, so the buffered fluid becomes less alkaline.
- **Neutrality itself falls**: neutral water is pH 7.00 at 25 °C but about
**pH 5.85 at 150 °C**.
So the meaningful quantity is the **alkaline margin**, $\text{pH}(T) - \text{pH}_{neutral}(T)$,
not the raw pH. Use [`AmineBufferedPH`](../../../src/main/java/neqsim/process/corrosion/AmineBufferedPH.java).
**2. Do not confuse FAC with erosion-corrosion.** They occur at the same
locations and need *different* mitigation:
| | FAC | Erosion-corrosion |
|---|---|---|
| Mechanism | Electrochemical dissolution, mass-transfer limited | Mechanical removal by particles/cavitation |
| Surface | Smooth, wavy, scalloped | Directional grooves, impingement craters |
| Fix | Chemistry, temperature, Cr alloying | Remove particles / impingement |
`RootCauseAnalyser` now raises both as separate candidates.
+ **3. Do not read a CFD wall-shear map as a FAC map at a separated feature.**
+
+ FAC is mass-transfer controlled. `FlowAcceleratedCorrosion` gets there through
+ Berger-Hau, $Sh = 0.0165\,Re^{0.86}Sc^{0.33}$, with a Stokes-Einstein diffusivity —
+ for a hot glycol/water loop $Sc$ lands near **280**, so the concentration boundary
+ layer is roughly $Sc^{1/3}\approx 6.5$ times thinner than the momentum one.
+
+ CFD studies usually deliver wall shear, and the tempting conversion is
+ $k_m\propto u^{*}\propto\sqrt{\tau_w}$. **That is only valid where the boundary layer
+ stays attached** — a bend, a gentle taper. At a weld root protrusion, an orifice or
+ any sudden expansion the flow separates and reattaches, and **at reattachment
+ $\tau_w$ passes through zero while $k_m$ peaks**. A shear map there puts its minimum
+ close to where the metal loss is worst, so:
+
+ - a shear-derived geometry factor is defensible for `ELBOW_BEND`, **not** for
+ `WELD_ROOT_PROTRUSION` or `DOWNSTREAM_ORIFICE`;
+ - a low-shear separated wake in a CFD figure must not be described as low-risk.
+
+ To compute a weld factor honestly you need a passive scalar at the real $Sc$ on a
+ wall-resolved mesh, validated by reproducing the Berger-Hau $Sh$ in a straight run
+ first — the mass-transfer analogue of checking the straight-pipe $\tau_w$. The
+ `cfd-coupling` skill solves momentum only today, so state the screening factor and
+ its basis rather than substituting a shear ratio.
+
## Workflow
### 1. Get fluid properties from the actual fluid
Do not use water tables — glycol changes density and viscosity substantially,
and viscosity roughly halves between 100 °C and 150 °C, which nearly doubles
the Reynolds number at constant velocity.
```java
SystemInterface f = new SystemSrkCPAstatoil(273.15 + 150.0, 19.6);
f.addComponent("TEG", 45.0, "kg/sec");
f.addComponent("water", 55.0, "kg/sec");
f.setMixingRule(10);
new ThermodynamicOperations(f).TPflash();
f.initProperties();
double rho = f.getDensity("kg/m3");
double mu = f.getViscosity("cP");
```
### 2. Convert laboratory pH to in-situ pH
```java
AmineBufferedPHResult ph = new AmineBufferedPH()
.setAmine(BufferAmine.DEA)
.setMeasuredPH(8.7, 20.0) // lab value and lab temperature
.setOperatingTemperature(150.0)
.setGlycolMassFraction(0.45) // records a warning; not corrected
.calculate();
ph.getOperatingPH(); // in-situ pH at 150 C
ph.getMarginAtOperating(); // the number that matters
ph.getVerdict(); // ROBUST / ADEQUATE / MARGINAL / INSUFFICIENT
```
+ ### 2b. Ask how much buffer is left, not just how much margin
+
+ A positive margin does not say whether it sits on a fresh buffer or on the remnant of
+ a nearly exhausted one, and those call for different actions. `calculateAlkalineReserve`
+ locates the titration end point — the laboratory pH at which the margin at the
+ operating temperature reaches zero — and reports how much of the usable reserve has
+ already been consumed. The amine concentration cancels out, so **no dosing record is
+ needed**: a fluid sample is enough.
+
+ ```java
+ AmineBufferedPH calc = new AmineBufferedPH()
+ .setAmine(BufferAmine.DEA)
+ .setMeasuredPH(8.7, 20.0)
+ .setOperatingTemperature(150.0)
+ .setGlycolMassFraction(0.45);
+
+ // 310 mg/L total organic acids, formate/acetate average molar mass 52.03 g/mol
+ AlkalineReserveResult r = calc.calculateAlkalineReserve(310.0, 52.03);
+
+ r.getMeasuredPHAtZeroMargin(); // 8.33 - the real control floor, not pH 7
+ r.getFreeBaseFractionAsFound(); // 0.31
+ r.getReserveSpentFraction(); // 0.82 - four fifths already gone
+ r.getRemainingAcidCapacityMgPerL(); // 68 mg/L of further acid
+ r.getRemainingAcidCapacityMmolPerL(); // 1.31 mmol/L - also prices a CO2 ingress
+ r.getDerivedAmineInventoryMmolPerL(); // cross-check against the dosing record
+ ```
+
+ Call `calculateAlkalineReserve()` with no arguments when no acid analysis exists; the
+ fractions still come out, only the capacity fields are NaN. Use
+ `AmineBufferedPH.freeBaseFraction(pH, pKa)` to draw the titration curve.
+
+ **Why this changes the recommendation.** A margin of +0.37 reads as a small but
+ positive number. Expressed as a reserve it is the span from pH 8.7 down to pH 8.33,
+ with 82 % already spent — so total organic acid belongs in the control limits, not in
+ a trend plot, and a single sub-9 pH excursion is most of what is left.
+
+ ### 2c. Price a CO2 or O2 ingress against that reserve
+
+ Dissolved CO2 titrates the same buffer mole for mole at these pH values, and O2
+ titrates it indirectly by oxidising the glycol to organic acids. Both therefore
+ convert into the same mmol/L currency as the remaining capacity. Get the solubility
+ from a flash of the actual glycol/water rather than a water table, and ask for the
+ concentration unit directly:
+
+ ```java
+ double hCO2 = fluid.calcHenrysConstant("CO2", "mol/m3/bar"); // == mmol/L/bar
+ double hO2 = fluid.calcHenrysConstant("oxygen", "mol/m3/bar");
+ double dissolvedCO2mmolPerL = hCO2 * partialPressureBar;
+ ```
+
+ Supported units are `bar` (the default, `f_i / x_i` per mole fraction), `mol/m3/bar`,
+ `mmol/L/bar`, `mol/L/bar` and `mg/L/bar`. **One mol/m3 is one mmol/L** — dividing by
+ 1000 between them is the most common error in this calculation, which is why both
+ spellings are accepted. The method needs exactly two phases and throws rather than
+ returning zero if that is not the case.
+
### 3. Rank the FAC contributors
```java
FlowAcceleratedCorrosionResult fac = new FlowAcceleratedCorrosion()
.setFlow(2.66, 0.025)
.setFluidProperties(rho, mu)
.setTemperature(150.0)
.setInSituPH(ph.getOperatingPH()) // in-situ, never the lab value
.setGeometry(FacGeometry.WELD_AT_BEND)
.setChromiumContent(0.02) // carbon steel; P11 is 1.25
.calculate();
fac.getDominantFactor(); // which lever actually controls the outcome
fac.getWallShearStressPa();
fac.ratioTo(otherCase); // quantify a proposed change
```
The index is **for comparison only** — ratios between cases are meaningful, the
absolute value is not a wall-loss rate.
## Things worth checking that investigations routinely miss
| Check | Why |
|---|---|
| **Express a velocity exceedance as shear** | $\tau \propto v^{1.75}$, so a 3 % velocity overshoot is a ~13 % shear overshoot. A "3 %" framing makes a real exceedance look like noise |
| **Correlate damage with the hot end** | Re rises ~70 % from 100 → 150 °C at constant velocity, and 150 °C is the solubility peak. Damage should concentrate at the outlet end — a cheap, testable prediction |
| **Check the filter micron rating** | Magnetite fines are 1–10 µm. An 80 µm element removes essentially none of them. "Improve filtration" must carry a rating |
| **Check the boiling margin** | Compute the bubble point; if bulk boiling is impossible, that hypothesis is closed off |
| **Flow reduction is not free** | Cutting flow to reduce shear reduces recovered duty, and at fixed duty raises metal temperature *towards* the 150 °C peak. Quantify the trade-off rather than asserting it |
+ | **Ask what the loop actually ran at** | A design basis says what the flow *should* be in stand-by; only the historian says how long it was there. See below — this is usually the cheapest decisive evidence in the whole study |
+ ### Measure the exposure instead of assuming it
+
+ A closed heating-medium loop is usually served by two or more identical units on
+ an N+1 duty/stand-by rota, and the stand-by one runs at a small fraction of design
+ flow. That makes the loop a natural experiment: same fluid, same pH history, same
+ material, different duty. If some units have leaked and others have not, the
+ historian settles whether duty is the difference.
+
+ Resolve the tag family from the plant's tag database (all three of flow, outlet
+ temperature and outlet pressure exist for each unit), then report, per unit:
+
+ - the **fraction of live-loop time below each design threshold** — the stand-by
+ flows the data sheet specifies, and the min-flow protection levels;
+ - the **median flow as a fraction of design**;
+ - the **maximum outlet temperature** against the high-temperature protection
+ setting and the data sheet film limit.
+
+ On one WHRU loop this turned "the unit that runs continuously has not leaked" from
+ an absence of maintenance records into a measured 4 % versus 40-46 % of time below
+ 20 % of design flow. It also **removed** a competing hypothesis: cycle count did
+ not discriminate at all, which corroborated a separate fatigue screening.
+
+ See `enterprise-plant-data` for the unit-reconciliation, outage-exclusion and
+ cycle-aliasing traps that decide whether those percentages mean anything.
+
+ ### Find out how the bend is actually built before modelling it
+
+ Damage reported "at circumferential welds adjacent to bends" is a construction
+ question first and a fluid-dynamics question second. Retrieve the bundle
+ description and the *Return bends* block of the equipment data sheet before
+ assuming anything:
+
+ | What to look for | Why it changes the analysis |
+ |---|---|
+ | **Bend angle** | A 180° return is the norm in serpentine coils, not a 90° elbow. Dean secondary flow needs roughly a quarter to a half turn to develop, so a 90° case releases the flow before the vortex pair is established and **understates** both the extrados enhancement and its downstream persistence. A geometry factor computed on 90° is a lower bound for a 180° return |
+ | **Formed bend or separate fitting** | If the data sheet says the return bends are *forged fittings* (e.g. ASTM A234 WPB) rather than formed tube, then a circumferential butt weld exists at each end of every bend **by construction**. `WELD_AT_BEND` stops being a screening assumption and becomes the documented geometry |
+ | **Fitting grade vs tube grade** | A106 Gr. B tube welded to an A234 WPB fitting is a dissimilar-heat joint. Neither grade specifies chromium, and FAC rate is controlled by residual Cr at the **hundredths of a percent** level, so the lower-Cr side wastes preferentially and produces sharp thinning at the weld rather than general loss. The material certificates carry the analysis — this is a document retrieval, not a study |
+ | **Bend radius** | Frequently absent from the data sheet. If no *R*/*D* is documented, say so; do not let an assumed long-radius default pass as a retrieved value |
+
+ **Provenance trap that produced this entry.** A CFD script carried
+ `bend_angle_deg = 90.0` and `BEND_RADIUS_RATIO = 1.5` under a block comment
+ reading "all from the task (data sheet geometry)". The bore genuinely was from the
+ data sheet; the bend was not, and the controlled documents said 180°. A comment
+ that covers a block of constants can be true for one line and false for the next —
+ **source each geometry constant individually**, and put the document number next to
+ it rather than at the top of the block.
+
+ **And the angle moves where you inspect.** Re-solving that case at the documented
+ 180° changed more than the number. At *R*/*D* = 1.5, Re ≈ 1.7 × 10⁵:
+
+ | | 90° bend | 180° return |
+ |---|---|---|
+ | Peak wall shear ratio | 2.33 | 2.74 |
+ | Geometry factor √R | 1.53 | 1.66 |
+ | **Where the peak sits** | intrados, near the entry | **55° off the intrados, past mid-turn** |
+
+ Over a half turn the Dean vortex pair becomes fully developed and convects
+ high-momentum core fluid outward along the side walls, so the maximum migrates off
+ the intrados towards the quarter position and is delayed to beyond the mid-point of
+ the arc. Downstream over 15–25 D the pattern inverts — extrados ≈ 1.5, intrados
+ ≈ 0.9 in the separated wake. **Inspecting the intrados entry, which is the right
+ answer for a 90° elbow, is the wrong answer for a 180° return.**
+
## Material upgrade
About 1 % Cr gives roughly an order-of-magnitude improvement. NORSOK M-001
specifies **ASTM A335 P11** for WHRU heat-exchanger tubes; API RP 571 and API RP
661 both point to low-alloy Cr-Mo steel for FAC-prone service. If plain carbon
steel is installed where a standard specifies P11, that is a compliance finding,
not just an observation — check it explicitly with `neqsim-standards-lookup`.
## Reporting
`results.json` should carry: `in_situ_pH`, `alkaline_margin`, `wall_shear_stress_Pa`,
`fac_index_ratio` for each case compared, `dominant_factor`, and every entry of
`getWarnings()` in the assumptions/gaps register. Declare the ideal-solution
basis of the pH shift and the comparison-only nature of the FAC index.
## Related skills
- `neqsim-flow-assurance` — CO2/H2S corrosion in production systems (a *different* mechanism; NORSOK M-506 does not apply to a CO2-free closed loop)
- `neqsim-root-cause-analysis` — ranking FAC against other candidates
- `neqsim-standards-lookup` — NORSOK M-001, API RP 571 §3.9, API RP 669, API RP 661
- `neqsim-self-heating-ignition` — the same Arrhenius framework applied to glycol oxidative degradation, which generates the organic acids that consume alkalinity
+ - `neqsim-plant-data` / `enterprise-plant-data` — measured stand-by exposure, the duty comparison between units, and the traps in quoting "% of design flow"
+ - `enterprise-maintenance-api` — leak distribution per tag and equipment-availability history (filter outages), which pairs with the historian evidence