name: taipower-indoor-wiring-ampacity
description: "This skill should be used when calculating or verifying the allowable ampacity (current-carrying capacity) of indoor electrical wiring and conduit fill limits according to the Taipower Indoor Wiring Regulations (屋內線路裝置規則)."
+ metadata:
+ class: B
---
# Taipower Indoor Wiring Ampacity & Conduit Fill
## Context & Purpose
This skill encodes the regulations for indoor electrical wiring (屋內線路裝置規則) specifically focusing on the allowable ampacity of wires inside conduits (PVC or Metal) and ambient temperature corrections.
## Parameters & Tables (Based on Article 16)
### 1. Baseline Conditions
- **Standard Ambient Temperature**: 35°C
- **Standard Conductor Insulation Temp**: 60°C (e.g., PVC), 75°C (e.g., XLPE/PE), or 90°C.
- **Wire Material**: Copper (銅)
### 2. Ampacity for PVC Wire in Conduit (60°C Insulation, 35°C Ambient) - Partial Table (Table 16-7)
| Wire Size (mm²) | Ampacity for ≤ 3 wires | Ampacity for 4 wires | Ampacity for 5-6 wires |
|-----------------|------------------------|----------------------|------------------------|
| 2.0 mm (Solid) | 19 A | 16 A | 14 A |
| 3.5 mm² | 19 A | 16 A | 14 A |
| 5.5 mm² | 25 A | 23 A | 20 A |
| 8 mm² | 33 A | 30 A | 25 A |
| 14 mm² | 50 A | 40 A | 35 A |
| 22 mm² | 60 A | 55 A | 50 A |
| 38 mm² | 85 A | 75 A | 65 A |
| 50 mm² | 100 A | 90 A | 80 A |
| 100 mm² | 160 A | 150 A | 125 A |
*(Note: Neutral wire, grounding wire, and control wires are generally not counted in the "number of wires" for ampacity derating, unless harmonics are present).*
### 3. Voltage Drop (Article 9)
- **Feeder + Branch Circuit**: Total voltage drop must not exceed **5%** of the nominal voltage.
- **Feeder only or Branch only**: Voltage drop must not exceed **3%**.
## Execution Logic for AI
When reviewing a single-line diagram (單線圖) or wiring schedule:
1. Identify the wire size (e.g., 8 mm²) and the number of current-carrying conductors in the conduit.
2. Cross-reference with the ampacity table to find the maximum allowed current.
3. Compare the allowed current with the specified breaker size (AT/AF). The wire's ampacity must be ≧ the breaker's trip setting (AT), with exceptions for motor loads.
4. Verify voltage drop calculations do not exceed 3% for branches or 5% total.