name: neqsim-relief-flare-network
version: "1.0.0"
description: "Relief and flare system design — PSV sizing per API 520 (gas/liquid/two-phase, fire case), API 521 fire heat input, flare load summation, flare-tip sizing, radiation contour (API 521 §6), header back-pressure & Mach, and the integrated TR3001 overpressure-protection study engine (multi-cause governing-case selection, fire-case relief, compliance check, disposal-load roll-up). USE WHEN: a task involves PSV sizing, relief contingency analysis, thermal relief for trapped liquid, flare network hydraulics, flare radiation/dispersion, PSV→flare integration, or a TR3001/API 521 overpressure study. Anchors on neqsim.process.util.fire.ReliefValveSizing, neqsim.process.safety.overpressure, neqsim.process.equipment.flare.{Flare, FlareStack}, neqsim.process.equipment.valve.SafetyValve."
last_verified: "2026-06-27"
requires:
java_packages: [neqsim.process.util.fire, neqsim.process.safety.overpressure, neqsim.process.equipment.flare, neqsim.process.equipment.valve]
---
# NeqSim Relief & Flare Network Skill
End-to-end relief design — from individual PSV sizing through plant-wide load
summation, flare-tip selection, and radiation/dispersion checks per **API 520**,
**API 521**, **API 537**.
## When to Use
- Sizing a single PSV (gas / liquid / two-phase / fire case)
- Checking whether a blocked-in liquid segment needs thermal relief or source-term
handoff after rupture screening
- API 521 fire heat input on wetted area
- Aggregating simultaneous relief loads to a flare header
- Flare tip diameter and stack height (radiation)
- Header hydraulics: back-pressure on PSVs, Mach < 0.7
- Sour-gas dispersion check (toxic clouds)
Standards: **API 520 Part I/II**, **API 521** (relief contingencies + radiation),
**API 537** (flare equipment), **NFPA 30**, **EN ISO 23251**.
## Pattern 1 — Gas-phase PSV (API 520)
```java
import neqsim.process.util.fire.ReliefValveSizing;
import neqsim.process.util.fire.ReliefValveSizing.PSVSizingResult;
PSVSizingResult psv = ReliefValveSizing.calculateRequiredArea(
massFlowRate_kgs,
setPressure_barg,
backPressure_barg,
T_K,
MW,
k_cpcv, // ratio of specific heats
Z_compressibility,
overpressure_frac, // 0.10 process, 0.21 fire
Kd // discharge coeff (0.975 typical)
);
double area_m2 = psv.getRequiredArea();
String orifice = psv.getRecommendedOrifice(); // API 526 letter
String issues = ReliefValveSizing.validateSizing(psv, /*fire*/ false);
```
## Pattern 2 — Fire Case (API 521)
```java
double Q_fire_W = ReliefValveSizing.calculateAPI521FireHeatInput(
wettedAreaM2,
/*hasDrainage*/ true,
/*hasFireProofInsulation*/ false
);
// Mass flow = Q_fire / latent heat at relieving conditions
double mdot = Q_fire_W / latentHeat_J_per_kg;
PSVSizingResult psv = ReliefValveSizing.calculateRequiredArea(
mdot, setP, backP, T_relief, MW, k, Z,
/*overpressure_frac*/ 0.21, // fire allows 21%
Kd
);
```
API 521 fire equation: **Q = C × F × A_wet^0.82** with credit factors for drainage / insulation.
## Pattern 3 — Liquid PSV (API 520 Part I §5.8)
```java
import neqsim.process.util.fire.ReliefValveSizing.LiquidPSVSizingResult;
LiquidPSVSizingResult lpsv = ReliefValveSizing.calculateLiquidReliefArea(
volumeFlowRate_m3s,
setPressure_barg,
backPressure_barg,
rho_kg_m3,
viscosity_cP,
Kd
);
```
## Pattern 4 — Two-Phase (Omega Method)
```java
double area = ReliefValveSizing.calculateTwoPhaseReliefArea(
massFlow_kgs, setP_barg, backP_barg, omega, rho_relief, Kd
);
```
## Pattern 4b — Integrated Overpressure Study (TR3001 / API 521)
For a full overpressure-protection study on one protected item — enumerate
credible relief contingencies, pick the governing case, size the PSV, and check
acceptance — use `neqsim.process.safety.overpressure`. Each cause calculator is
fluent and returns an immutable `ReliefScenario`; the engine selects the
maximum-rate credible scenario and sizes accordingly (vapour via `ReliefValveSizing`
API 520; liquid via the API 520 liquid method; two-phase via the omega method).
```java
import neqsim.process.safety.overpressure.*;
// 1. Cause scenarios (fluent → ReliefScenario)
ReliefScenario blocked = new BlockedOutletRelief().setName("Blocked gas outlet")
.setInflowRateKgPerHr(36000.0).setReliefPressureBara(50.0)
.setReliefTemperatureC(20.0).setFluid(gas).calculate();
ReliefScenario fire = new FireCaseRelief().setName("Pool fire")
.setVesselDiameterM(2.0).setWettedHeightM(3.0) // or setWettedAreaM2(..)
.setHasDrainage(true).setHasFireFighting(true)
.setLatentHeatJPerKg(350000.0).setReliefPressureBara(60.0)
.setReliefTemperatureC(120.0).setFluid(gas).calculate();
// 2. Engine: governing case + sizing + acceptance
ProtectedItem item = new ProtectedItem("V-100", 100.0) // tag, MAWP [bara]
.setReliefSetPressureBara(100.0).setBackPressureBara(1.5);
OverpressureStudyResult result = new OverpressureProtectionStudy(item)
.addScenario(blocked).addScenario(fire).evaluate();
result.getGoverningScenario().getName(); // worst credible case
result.getRequiredAreaIn2(); // API 526 required orifice area
result.getRecommendedOrifice(); // orifice letter
result.isCapacityAdequate(); // area-based adequacy
result.getAcceptance().getAccumulationFraction(); // vs 1.10 / 1.16 / 1.21
// 3. TR3001 compliance findings (PASS/FAIL/NEEDS_REVIEW)
List<ComplianceFinding> findings = new TR3001ComplianceChecker().check(result);
boolean compliant = new TR3001ComplianceChecker().isCompliant(findings);
// 4. Roll relief loads up to a disposal header (API 521 §5.3)
ReliefDisposalResult disposal = new ReliefDisposalNetwork("Fire zone 1")
.addRelief(resultA, true).addRelief(resultB, true).calculate();
disposal.getTotalSimultaneousKgPerS(); // simultaneous header load
disposal.getPeakSingleKgPerS(); // largest single contributor
disposal.getGoverningContributor();
```
- Cause calculators: `BlockedOutletRelief`, `CheckValveLeakRelief`,
`ControlValveFailureRelief`, `TubeRuptureRelief`, `FireCaseRelief`.
- Set `ReliefScenario` phase to `LIQUID` (with `densityKgPerM3`/`viscosityPaS`)
or `TWO_PHASE` (with `gasMassFraction`, `gasDensityKgPerM3`,
`liquidDensityKgPerM3`, `latentHeatJPerKg`, `liquidHeatCapacityJPerKgK`) to
trigger the matching sizing path; missing two-phase inputs are reported as warnings.
- Accumulation limits: 1.10 single non-fire, 1.16 multiple, 1.21 fire (ASME VIII Div 1).
- Verified by `OverpressureProtectionStudyTest` + `OverpressureExtensionsTest`.
> **Adequacy is judged by AREA**, not by re-plugging the selected area into the
> nozzle equation: `calculateRequiredArea` (API 520 empirical) and the nozzle
> capacity formula use different coefficient bases and are not inverses.
## Pattern 5 — Flare Tip & Stack (API 537 + 521 §6)
```java
import neqsim.process.equipment.flare.Flare;
Flare flare = new Flare("MainFlare");
flare.setInletStream(reliefStream);
flare.setRadiantFraction(0.30); // typical 0.20–0.40
flare.setTipDiameter(0.5); // m
flare.setDesignHeatDutyCapacity(150.0, "MW");
flare.run(UUID.randomUUID());
// Radiation at ground distance
double q_Wm2 = flare.estimateRadiationHeatFlux(75.0); // 75 m
double dSafe = flare.radiationDistanceForFlux(4730.0); // K = 1.5 kW/m² × 4 hr exposure
```
API 521 §6.4 radiation criteria:
| Receiver | Allowable flux (kW/m²) |
| ---------------------------------- | --------------------------- |
| Personnel — emergency only | 9.46 |
| Personnel — escape (≤1 min) | 6.31 |
| Property line / 2-min escape | 4.73 |
| Solar background | ~1.0 (subtract from above) |
### Pattern 5b — Detailed Flare Flame & Sterile-Zone (API 537)
For sterile-zone radii, wind-tilted flame geometry, and flare noise, use
`Api537FlareFlameModel` (Kent 1968 flame length + tilt + iso-flux solver):
```java
import neqsim.process.safety.fire.Api537FlareFlameModel;
Api537FlareFlameModel flame = new Api537FlareFlameModel(
50.0, // relief mass flow [kg/s]
50.0e6, // heat of combustion [J/kg]
0.20, // radiant fraction
200.0) // tip exit velocity [m/s]
.setStackHeightM(40.0)
.setWindSpeedMPerS(10.0);
double lFlame = flame.flameLengthM();
double tilt = flame.flameTiltRad();
double r158 = flame.sterileZoneRadiusM(Api537FlareFlameModel.FLUX_1_58_KW); // ~personnel continuous
double r473 = flame.sterileZoneRadiusM(Api537FlareFlameModel.FLUX_4_73_KW); // property line
double r946 = flame.sterileZoneRadiusM(Api537FlareFlameModel.FLUX_9_46_KW); // emergency-only
double q75 = flame.heatFluxAtGroundDistance(75.0); // W/m²
double pwl = flame.soundPowerLevelDb();
double spl = flame.soundPressureLevelDb(100.0);
```
Verified by `Api537FlareFlameModelTest`. Radii are nested (lower flux reaches
further); flame tilts downwind and the tip moves horizontally with wind speed.
## Pattern 6 — Plant Load Summation
For each contingency (general power failure, total reflux failure, fire zone):
1. List PSVs that lift simultaneously
2. Sum mass flows at each PSV at its **relieving** conditions
3. Pick the **governing** contingency (highest header load)
4. Size the flare for that load
```java
double totalReliefLoad = psvs.stream()
.filter(p -> isActiveDuring(p, contingency))
.mapToDouble(p -> p.getMassFlowCapacity())
.sum();
```
For **simultaneous blowdown** contingencies (multiple BDVs into one header), use
`MultiVesselBlowdownStudy` (see `neqsim-depressurization-mdmt`) — it superimposes
the transient blowdown curves on a common time grid and reports the **peak**
combined header mass flow and the header Mach at that instant, which is the load
that actually sizes the header.
## Pattern 7 — Header Back-Pressure & Mach
For balanced-bellows / pilot-operated PSVs, verify:
- Built-up back-pressure ≤ 50% set (conventional 10%)
- Header Mach < 0.7 at any location (avoid critical flow choking design)
```java
import neqsim.process.equipment.valve.SafetyValve;
SafetyValve sv = new SafetyValve("PSV-101", inletStream);
sv.setSetPressure(120.0, "barg");
sv.setBackPressure(15.0, "barg");
sv.run();
double KbCorrection = sv.getBackPressureCorrectionFactor(); // > 0.6 for balanced PSV
```
## Pattern 8 — Dispersion of Unignited Release
```java
FlareDispersionSurrogateDTO disp = flare.getDispersionSurrogate();
// Use to bound H2S / SO2 ground concentration vs. IDLH/ERPG-2
```
For a governed production-readiness record, use
`neqsim.process.engineering.safety.FlareConsequenceCalculation`. It combines explicit
point-source radiation, neutral Gaussian centerline dispersion, spherical noise spreading,
and tip-Mach constraints in one typed result with uncertainty and provenance. Set
`productionQualification=true` only with standards/evidence references and
`consequenceMethodApplicability=approved`. This is a screening interface, not a substitute
for validated complex-terrain, stability-class, toxic, combustion, or detailed acoustic
modeling.
## Common Mistakes
| Mistake | Fix |
| --------------------------------------------------------- | -------------------------------------------------------------------- |
| Sizing fire PSV at 10% overpressure | Fire case uses 21%; non-fire is 10% (API 520) |
| Wetted area = total surface | API 521 wetted area is liquid-touching surface up to 7.6 m elevation |
| Ignoring drainage credit | F factor reduces Q_fire by 0.5 with adequate drainage (slope ≥ 1°) |
| Adding all PSV capacities for header | Use the governing **contingency**, not sum of nameplate capacities |
| K_d = 1.0 | Typical: gas/vapor 0.975, liquid 0.65, certified two-phase ≤ 0.85 |
| Ignoring Mach in header | Mach > 0.7 → choking, can dramatically raise back-pressure on PSVs |
| Using inlet line ΔP > 3% set | API 520 §7.3: > 3% inlet ΔP causes valve chatter, fix the piping |
| Picking smallest API 526 letter that meets area | Always pick the **next** letter for spare margin & spare-parts pool |
## Validation Checklist
- [ ] Each contingency has a documented worst-case mass flow
- [ ] Wetted-area calculation shows boundary up to 7.6 m
- [ ] Drainage / insulation credits supported by P&ID review
- [ ] Header sized so Mach < 0.7 at peak load
- [ ] Built-up back-pressure ≤ 10% (conventional) or ≤ 50% (balanced) of set
- [ ] Inlet line ΔP < 3% of set pressure
- [ ] Flare radiation ≤ 4.73 kW/m² at property line (incl. solar)
- [ ] Dispersion check at flame-out (toxic species)
- [ ] Results saved to `results.json` under `relief_system` with PSV table + flare load summary
## Related Skills
- [`neqsim-process-safety`](../neqsim-process-safety/SKILL.md) — when PSV is the IPL of last resort in LOPA
+ - [`neqsim-firewater-deluge-design`](../neqsim-firewater-deluge-design/SKILL.md) — fire-water demand for the area, which competes with the relief and flare load for the same simultaneous-demand budget
- [`neqsim-trapped-liquid-fire-rupture`](../neqsim-trapped-liquid-fire-rupture/SKILL.md) — blocked-in liquid fire rupture screening before thermal relief/PFP decisions
- [`neqsim-depressurization-mdmt`](../neqsim-depressurization-mdmt/SKILL.md) — blowdown transients + `MultiVesselBlowdownStudy` for coupled header loads
- [`neqsim-consequence-analysis`](../neqsim-consequence-analysis/SKILL.md) — `Api537FlareFlameModel` radiation/noise and hazardous-area zoning
- [`neqsim-dynamic-simulation`](../neqsim-dynamic-simulation/SKILL.md) — depressurization (blowdown) is separate from PSV
- [`neqsim-mechanical-design`](../neqsim-api-patterns/SKILL.md) — PSV mechanical via `SafetyValveMechanicalDesign`
- [`neqsim-standards-lookup`](../neqsim-standards-lookup/SKILL.md) — API 520 / 521 / 526 / 537