name: neqsim-firewater-deluge-design
- description: "Fire-water and deluge coverage design per NORSOK S-001 / ISO 13702 / NFPA 15 - application rates, area vs dedicated object protection, nozzle-net sizing, fire monitors with wind drift, hydraulic feasibility against an existing system, active-vs-passive substitution. USE WHEN: a task asks if an area has adequate deluge coverage, how many nozzles are needed, whether PFP or monitors can replace fire water, or whether a system can absorb a new deluge section."
- last_verified: "2026-09-12"
+ calculation_basis: "screening"
+ version: "0.2.0"
+ description: "Fire-water and deluge coverage design per NORSOK S-001 / ISO 13702 / NFPA 15: area versus dedicated object demand, nozzle-net sizing from flow and spacing, fire monitors with wind drift, hydraulic feasibility, active-versus-passive substitution. USE WHEN: a task asks if an area has adequate deluge coverage, how many nozzles are needed, or whether monitors or PFP can replace fire water."
+ last_verified: "2026-10-18"
+ requires:
+ python_packages: []
+ java_packages: [neqsim.process.safety.firewater]
+ env: []
+ network: []
---
- # Fire-water and deluge coverage design
+ # Fire-water and Deluge Coverage Design
- Sizing and adjudicating **active** fire protection for a process area. Complements
- `neqsim-consequence-analysis` (which sizes the fire), `neqsim-relief-flare-network`
- (which sizes the relief), and `neqsim-depressurization-mdmt` (which removes the
- inventory). This skill answers the question those three do not: *how much water,
- where, and is it even the right barrier?*
+ Use this skill for public, educational fire-water coverage screening. It turns a protected
+ area and an application rate into a water demand, a nozzle count and a grid pitch, and it
+ tests the two alternatives that get proposed whenever a fixed deluge net is inconvenient:
+ protecting the individual items instead of the area, and using fire monitors instead of a
+ fixed system.
- ## When to use
+ ## When to Use
- - A finding or a TTS/verification item says an area lacks deluge coverage.
- - A modification adds equipment to an area and the fire-water demand must be re-established.
- - Somebody proposes passive fire protection, or fire monitors, *instead of* deluge.
- - You must decide between blanket area coverage and dedicated object protection.
- - You need to know whether an existing fire-water system can take a new deluge section.
+ - A verification finding says an area lacks active fire protection and the demand must be scoped.
+ - A modification adds hydrocarbon-bearing equipment to an area and the fire-water demand changes.
+ - Somebody proposes fire monitors, or passive fire protection, in place of deluge.
+ - You need a first nozzle count and grid pitch before a hydraulic network calculation.
- ## The four questions, in order
+ ## Inputs
+ - `protected_area_m2`: plan area for general area coverage, m².
+ - `area_rate_lpm_per_m2`: application rate, (l/min)/m². Public minima are 10 for process
+ areas and equipment surfaces and 20 for wellhead areas and riser balconies.
+ - `objects`: tuple of `(tag, surface_area_m2, rate_lpm_per_m2)` for dedicated protection.
+ - `duration_min`, `foam_concentrate_percent`, `simultaneous_area_factor`.
+ - Nozzle: `nozzle_k_lpm_per_sqrt_bar`, `nozzle_min_pressure_barg`, `max_spacing_m`,
+ `operating_pressure_barg`, `coverage_efficiency`.
+ - Monitor: `monitor_count`, `monitor_flow_lpm`, `wind_speed_m_s`, `fall_height_m`,
+ `characteristic_dimension_m`, `line_of_sight_obstructed`.
+
+ ## Outputs
+
+ - `area_demand_lpm`, `object_demand_lpm`, `total_demand_lpm`, `total_demand_m3_per_h`,
+ `water_volume_m3`, `foam_concentrate_m3`, `object_to_area_ratio`.
+ - `nozzle_count_from_flow`, `nozzle_count_from_coverage`, `nozzle_count`,
+ `governing_criterion`, `grid_spacing_m`, `delivered_density_lpm_per_m2`,
+ `pressure_adequate`, `density_met`.
+ - `nominal_density_lpm_per_m2`, `drift_displacement_m`, `wind_coverage_fraction`,
+ `effective_density_lpm_per_m2`, `verdict`.
+ - `assumptions` on every result.
+
+ ## Engineering Method
+
+ The Python class `FireWaterCoverageModel` uses open, published relations only.
+
+ - Demand is the application rate times the protected area, plus the sum of dedicated
+ object surfaces times their rates, times a simultaneous-release factor.
+ - Nozzle discharge follows the orifice law $Q = K\sqrt{p}$ with $K$ in
+ $(\mathrm{l/min})/\sqrt{\mathrm{bar}}$.
+ - The nozzle count is the **larger** of the flow criterion (total discharge must meet the
+ density) and the coverage criterion (area divided by the square of the maximum permitted
+ spacing). Sizing on flow alone is the classic error: it gives too few, too widely spaced
+ nozzles that meet the average density but leave dry patches.
+ - Monitor droplets are drifted downwind by $\Delta x = h\,u_{\mathrm{wind}}/v_t$, and the
+ coverage loss is taken as linear in the drift over the characteristic target dimension.
+ - Shadowing is a flag, not a model: a monitor cannot wet a surface it cannot see.
+
+ ## Python Usage Pattern
+
+ ```python
+ from firewater_deluge_design import FireWaterCoverageModel
+
+ model = FireWaterCoverageModel()
+
+ demand = model.demand(
+ protected_area_m2=420.0,
+ area_rate_lpm_per_m2=10.0,
+ objects=(("20-VA-001", model.horizontal_vessel_surface_m2(3.0, 9.0), 10.0),),
+ duration_min=30.0,
+ )
+ print(demand.total_demand_m3_per_h, demand.object_to_area_ratio)
+
+ layout = model.deluge_layout(
+ protected_area_m2=420.0,
+ required_density_lpm_per_m2=10.0,
+ nozzle_k_lpm_per_sqrt_bar=57.0,
+ nozzle_min_pressure_barg=2.0,
+ max_spacing_m=3.7,
+ operating_pressure_barg=3.5,
+ )
+ print(layout.nozzle_count, layout.governing_criterion, layout.grid_spacing_m)
+
+ monitors = model.monitor_screening(
+ target_area_m2=420.0,
+ required_density_lpm_per_m2=10.0,
+ monitor_count=2,
+ monitor_flow_lpm=2400.0,
+ wind_speed_m_s=12.0,
+ fall_height_m=12.0,
+ )
+ print(monitors.effective_density_lpm_per_m2, monitors.verdict)
+ ```
+
+ ## The Four Questions, in Order
+
Answer them in this order. Reversing the order is the usual way these studies go wrong.
- 1. **What fire are we protecting against?** Get this from `neqsim-consequence-analysis`.
- A pressurised **gas jet fire** is not extinguished by water — the creditable function
- is cooling of exposed surfaces and control of escalation. A **liquid pool fire** can be
- controlled and extinguished by foam-water. If the area is labelled "gas" but holds lube
- and seal-oil tanks, the pool-fire case is still live and is a common omission.
+ 1. **What fire are we protecting against?** A pressurised **gas jet fire** is not
+ extinguished by water; the creditable function is cooling of exposed surfaces and
+ control of escalation. A **liquid pool fire** can be controlled and extinguished by
+ foam-water. An area labelled "gas" that holds lube and seal-oil tanks still has the
+ pool-fire case live, a common omission. Take the fire from `neqsim-consequence-analysis`.
2. **Can the inventory be removed faster than the target fails?** NORSOK S-001 makes
blowdown the *primary* means of protecting a pressurised inventory. Run
`DepressurizationSimulator` against `PfpDemandCalculator.bareSteelTimeToCriticalS()`.
Thick-walled vessels frequently outlive the blowdown; thin support steel frequently
- does not — that asymmetry, not a blanket rule, is what decides where protection goes.
- 3. **What does the requirement actually demand?** See the requirement table below, and
- read the *edition* of the standard carefully (see "Traps").
- 4. **Only then**: size the water, lay out the nozzles, and test the hydraulics.
-
- ## Java API
+ does not, and that asymmetry decides where protection goes.
+ 3. **What does the requirement actually demand?** See the application-rate table and
+ the traps below, and read the *edition* of the standard carefully.
+ 4. **Only then:** size the water, lay out the nozzles, and test the hydraulics.
- `neqsim.process.safety.firewater` (Java 8, all classes `Serializable`, all emit
- schema-versioned JSON via `toJson()`).
+ ## Java API (`neqsim.process.safety.firewater`)
- > Do **not** use `FireProtectionDesign.firewaterDemand(...)`
- > (`neqsim.process.mechanicaldesign.designstandards`) for any of these questions. It
- > returns one lumped m³/h figure for the engineering-deliverables package and carries no
- > coverage, nozzle, monitor or hydraulic-feasibility logic.
+ Java 8, all classes `Serializable`, all emit schema-versioned JSON via `toJson()`. Do
+ **not** use `FireProtectionDesign.firewaterDemand(...)`
+ (`neqsim.process.mechanicaldesign.designstandards`) for these questions: it returns one
+ lumped m³/h figure and carries no coverage, nozzle, monitor or hydraulic-feasibility logic.
```java
// 1. demand: blanket area coverage
FireWaterDemandCalculator area = new FireWaterDemandCalculator(510.0)
.setAreaRate(FireWaterDemandCalculator.NORSOK_PROCESS_AREA_LPM_M2) // 10 (l/min)/m2
.setDurationMin(30.0)
.setFoamConcentratePercent(1.0);
double lpm = area.totalDemandLpm(); // 5100
double m3h = area.totalDemandM3PerHour(); // 306
double vol = area.waterVolumeM3(); // 153
// 1b. demand: dedicated object protection instead
FireWaterDemandCalculator obj = new FireWaterDemandCalculator(0.0).setAreaRate(0.0);
obj.addHorizontalVessel("HA-13-0001", 0.72, 6.606, 10.0); // shell OD, length, rate
double saving = 1.0 - obj.totalDemandLpm() / area.totalDemandLpm();
- // 2. nozzle net — governed by the LARGER of the flow and spacing criteria
+ // 2. nozzle net, governed by the LARGER of the flow and spacing criteria
DelugeNozzleLayout.Nozzle hv26 = new DelugeNozzleLayout.Nozzle(
"HV26", 42.9, 3.5, 3.0, 1.0); // K [(l/min)/sqrt(bar)], p_min, max spacing, clear depth
DelugeNozzleLayout net = new DelugeNozzleLayout(510.0, 10.0, hv26)
.setOperatingPressureBarg(5.0)
- .setCoverageEfficiency(1.0); // < 1.0 to tighten the grid for wind or shadowing
+ .setCoverageEfficiency(1.0); // < 1.0 tightens the grid for wind or shadowing
net.nozzleCountFromFlow(); // 54
net.nozzleCountFromCoverage(); // 57
- net.nozzleCount(); // 57 — coverage governs
+ net.nozzleCount(); // 57, coverage governs
net.governingCriterion(); // "coverage"
net.gridSpacingM(); // 2.99
net.isClearanceAdequate(0.8); // false for an HV nozzle needing 1.0 m
// 3. monitors as an alternative
FireMonitorCoverage mon = new FireMonitorCoverage(510.0, 10.0)
.setMonitors(4, 4000.0).setGeometry(40.0, 120.0)
.setWind(15.0, 12.0) // wind speed, droplet fall height
.setCharacteristicTargetDimensionM(25.5)
.setLineOfSightObstructed(true);
- mon.nominalDensityLpmPerM2(); // 31.4 — passes in still air
- mon.effectiveDensityLpmPerM2(); // 3.7 — fails once the pattern drifts
+ mon.nominalDensityLpmPerM2(); // 31.4, passes in still air
+ mon.effectiveDensityLpmPerM2(); // 3.7, fails once the pattern drifts
mon.verdict();
// 4. can the existing system take it?
FireWaterCoverageAssessment gate = new FireWaterCoverageAssessment(510.0, 5100.0)
.setCoveredAreaM2(0.0)
.setSpareSupplyFlowLpm(16748.0)
.setWorstCasePressureMarginBar(-0.9, "XX-71-0010B") // worst DESIGN case, not normal case
.setRequiredPressureMarginBar(0.5);
gate.verdict(); // SUPPLY_PRESSURE_DEFICIT
gate.recommendation();
- // 5. active vs passive — what the framework does and does not allow
+ // 5. active vs passive: what the framework does and does not allow
ActiveFireProtectionScreening s = new ActiveFireProtectionScreening(
ActiveFireProtectionScreening.FireScenario.GAS_JET_FIRE)
.setIncidentHeatFluxKWPerM2(200.0)
.setBlowdownTimeToTargetS(359.0)
.setBareSteelTimeToCriticalS(98.7)
.setLoadBearingStructureExposed(true)
.setNozzlesCanBePlacedAboveEquipment(false);
s.isWaterExtinguishing(); // false for a gas jet fire
- s.isPassiveSubstitutionPermitted(); // false — always
+ s.isPassiveSubstitutionPermitted(); // false, always
s.isBlowdownFasterThanFailure(); // false here: thin steel loses the race
s.rankedMeasures();
```
- ## Application rates
+ Validated by `FireWaterDesignTest` (orifice law, both nozzle-count criteria, wind-drift
+ model, verdict routing, JSON contract).
+ ## Application Rates
+
| Basis | Applies to | Rate |
|---|---|---|
| NORSOK S-001 Ed.4 §20.4.4 (Ed.5/6 §21) | Process areas **and equipment surfaces** | 10 (l/min)/m² |
| NORSOK S-001 Ed.4 §20.4.4 | Wellhead, riser balconies, FPSO turret manifolds | 20 (l/min)/m² |
| NORSOK S-001 Ed.4 §20.4.4 | Water at design pressure after a confirmed fire signal | ≤ 30 s |
| NFPA 15 | Exposure protection of vessel shells | 10.2 (l/min)/m² (0.25 gpm/ft²) |
| Common project practice | Enclosed utility/machinery rooms, sprinkler | 6 (l/min)/m² |
- `NORSOK S-001 does not state a fire-water duration.` Take the duration from the project
- basis (30 min is the usual foam figure and is often carried across), and say where it
- came from.
+ NORSOK S-001 does not state a fire-water duration. Take it from the project basis (30 min
+ is the usual foam figure and is often carried across) and say where it came from.
## Traps
- **Clause renumbering.** NORSOK S-001 **Ed.4 (2008)**: clause 20 = fire fighting systems,
clause 21 = escape and evacuation. **Ed.5 (2018) / Ed.6 (2020)**: clause 20 = passive fire
- protection, clause **21 = active fire protection**. A finding citing "21.4.4" is citing
+ protection, clause **21 = active fire protection**. A finding citing "21.4.4" cites
Ed.5/6. Check which edition the installation's own basis invokes before agreeing that a
- requirement applies. Ed.6's foreword states it is a modality-only revision of Ed.5.
- - **Fire water is never a substitute for passive fire protection.** The Norwegian Facilities
- Regulations §29 forbid taking credit for the cooling effect of fire-fighting equipment when
+ requirement applies.
+ - **Fire water never substitutes for passive fire protection.** The Norwegian Facilities
+ Regulations §29 forbid crediting the cooling effect of fire-fighting equipment when
designing PFP, and §11 forbids crediting fire water when establishing design accidental
- loads. NORSOK S-001 Ed.4 §19.4.2/§19.4.3 say the same. **The converse is also not permitted**:
- putting PFP on one item does not discharge an area fire-water requirement, because the
- requirement is written against the area.
- - **Design on flow alone and you will under-count the nozzles.** A high-K nozzle meets the
- density with few nozzles spaced far apart, leaving dry patches. Always take the larger of
- the flow and spacing counts.
+ loads (NORSOK S-001 Ed.4 §19.4.2/§19.4.3 say the same). **The converse is also not
+ permitted**: PFP on one item does not discharge an area fire-water requirement.
+ - **Flow alone under-counts nozzles.** A high-K nozzle meets the density with few nozzles
+ spaced far apart, leaving dry patches. Take the larger of the flow and spacing counts.
- **Take the pressure margin from the worst *design* case, not the normal case.** Mature
- fire-water systems are commonly pressure-limited, not flow-limited, and the margin can be
- negative in a two-pump case while looking healthy in the three-pump case.
- - **"Nozzles cannot go above the equipment" is not a reason to have no coverage.** It is a
- reason to use side-mounted nozzles or a dedicated spray ring. If a project basis excludes
- coverage over an item for maintenance reasons, that is a *deviation*, and it needs to be
- recorded and accepted as one.
+ fire-water systems are commonly pressure-limited, and the margin can be negative in a
+ two-pump case while looking healthy in the three-pump case.
+ - **"Nozzles cannot go above the equipment" is not a reason to have no coverage.** Use
+ side-mounted nozzles or a dedicated spray ring. A project basis that excludes coverage
+ over an item is a *deviation* and must be recorded and accepted as one.
- **Monitors are not equivalent to a fixed system.** NORSOK S-001 Ed.4 permits monitor
- substitution only for the turret, and §20.4.7 then binds monitors to the same density and
+ substitution only for the turret, and §20.4.7 binds monitors to the same density and
functionality. On an open deck, wind drift and shadowing usually settle the question.
- ## Chains to
+ ## Validation Checklist
- | Direction | Skill | Why |
- |---|---|---|
- | upstream | `neqsim-consequence-analysis` | fire type, heat flux, flame reach |
- | upstream | `neqsim-depressurization-mdmt` | blowdown time, the primary barrier |
- | upstream | `neqsim-technical-document-reading` | area geometry, nozzle K-factors, hydraulic report |
- | downstream | `neqsim-process-safety` | barrier register, performance standards, LOPA |
- | downstream | `neqsim-standards-lookup` | clause traceability into `results.json` |
- | downstream | `neqsim-professional-reporting` | figure→discussion→linked_results |
+ - [ ] The application rate comes from the governing project standard, not from the
+ default: 10 (l/min)/m² for process areas, 20 for wellheads and riser balconies.
+ - [ ] Object surfaces are exposed wetted surfaces, not plan footprints.
+ - [ ] The nozzle count reports `governing_criterion`; a flow-governed count has been
+ cross-checked against the maximum permitted spacing.
+ - [ ] `pressure_adequate` and `density_met` are both true, or the deficit is stated.
+ - [ ] The duration used for `water_volume_m3` is traceable to the project basis.
+ - [ ] Monitor results are reported with the wind speed they assume.
+ - [ ] The result is presented as a screening input to a hydraulic network calculation.
- ## Validation
+ ## Common Mistakes
- `src/test/java/neqsim/process/safety/firewater/FireWaterDesignTest.java` — 23 tests covering
- the orifice law, the two nozzle-count criteria, the wind-drift model, the verdict routing and
- the JSON contract.
+ | Symptom | Cause | Fix |
+ | --- | --- | --- |
+ | Nozzle count too low, dry patches in the area | Sized on the flow criterion alone | Take the larger of the flow and coverage counts; check `governing_criterion` |
+ | Higher-K nozzles do not reduce the count | The layout is spacing-governed | Reduce the protected area or accept the grid; `K` cannot fix overlap |
+ | Demand far below expectation | Object surfaces entered as footprints | Use exposed wetted surface, e.g. `horizontal_vessel_surface_m2()` |
+ | Monitor concept looks adequate | Screened at zero wind | Re-run at the design wind speed and report `verdict` |
+ | Passive fire protection reduced because deluge was added | Substitution applied in the wrong direction | Keep passive protection; the rule runs one way only |
+
+ ## Interpretation
+
+ - `object_to_area_ratio` well below 1 means selective protection of the hydrocarbon-bearing
+ items is far cheaper in water than blanket coverage. Whether it is *permitted* is a
+ requirement question, not a hydraulic one — the area-coverage requirement in NORSOK S-001
+ and ISO 13702 is written against the area.
+ - `governing_criterion == "coverage"` means the nozzle net is set by spray overlap, so a
+ higher-K nozzle will not reduce the count.
+ - `verdict == "marginal_wind_limited"` means the monitor concept only works in still air.
+
+ ## Limitations
+
+ - Screening only. It performs no network hydraulics, no trajectory modelling and no CFD.
+ - It does not decide compliance. Application rates, durations and the acceptability of
+ selective protection come from the governing project standard and the accepted deviations.
+ - It gives no credit for, and takes no credit from, passive fire protection. Fire water and
+ passive fire protection are complementary barriers, and the regulatory rule runs one way:
+ passive protection may not be reduced because active protection exists.
+
+ ## Related Skills
+
+ - `neqsim-consequence-analysis` — fire type, heat flux and flame reach (upstream).
+ - `neqsim-depressurization-mdmt` — blowdown time, the primary barrier (upstream).
+ - `neqsim-technical-document-reading` — area geometry, nozzle K-factors, hydraulic report (upstream).
+ - `neqsim-process-safety` — barrier register, performance standards, LOPA (downstream).
+ - `neqsim-standards-lookup` — clause traceability into `results.json` (downstream).
+ - `neqsim-jet-fire-radiation-screening` and `neqsim-relief-load-screening` — the fire side.
+ - `neqsim-depressurization-screening` — inventory removal, the primary barrier for a
+ pressurised system.
+ - `neqsim-safety-function-coverage-screening` — whether the protective functions exist at all.
+ - `neqsim-weather-data` — live or forecast `wind_speed_m_s` for the fire-monitor
+ wind-drift screening, instead of an assumed value.
+
+ ## References
+
+ - NORSOK S-001, Technical Safety — fire-water application rates and area coverage.
+ - ISO 13702, Control and Mitigation of Fires and Explosions on Offshore Production
+ Installations.
+ - NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection — nozzle spacing
+ and density.
+ - API RP 2030, Application of Fixed Water Spray Systems for Fire Protection in the
+ Petroleum and Petrochemical Industries.
+ - NeqSim repository: https://github.com/equinor/neqsim