name: neqsim-compressor-antisurge-recycle
- version: "1.0.0"
- description: "Anti-surge recycle and coordinated minimum-speed recycle control for centrifugal compressors in NeqSim: chart generation, anti-surge calculation, MinimumSpeedRecycleControllerStructure split-range control, fuel-gas, CO2 and cost savings. USE WHEN: a task must protect a compressor from surge, coordinate speed and recycle valve at minimum speed, stop uncoordinated recycle opening, or value power/CO2 savings from control optimization."
- last_verified: "2026-08-26"
+ calculation_basis: "neqsim-java"
+ version: 0.4.0
+ description: "Anti-surge recycle for centrifugal compressors in NeqSim: chart generation, AntiSurgeRecycleCalculator, dynamic AntiSurgeController, CompressorAntiSurgeApplication binding, MinimumSpeedRecycleControllerStructure split-range control, speed-solve convergence and recycle power/CO2 savings. USE WHEN: a task must protect a compressor from surge with a recycle loop, coordinate speed and recycle at minimum speed, or value avoided recycle."
+ last_verified: "2026-10-18"
requires:
- java_packages: [neqsim.process.equipment.compressor, neqsim.process.controllerdevice.structure, neqsim.process.controllerdevice]
+ python_packages: []
+ java_packages:
+ - neqsim
+ env: []
+ network: false
---
- # NeqSim Compressor Anti-Surge & Minimum-Speed Recycle Control Skill
+ # Compressor Anti-Surge Recycle Setup
- This skill provides patterns for anti-surge protection, minimum-speed recycle coordination, and energy/CO2 emission evaluations for centrifugal compressor recycle loops.
+ This skill explains how to protect a centrifugal compressor against surge in a
+ NeqSim `ProcessSystem` by adding a recycle (spill-back) loop. It covers the
+ preferred steady-state helper (`AntiSurgeRecycleCalculator`), the dynamic
+ reverse-acting PI controller (`AntiSurgeController`), and the application-level
+ supervisor (`CompressorAntiSurgeApplication`) that can bind directly to real
+ NeqSim topology objects such as a compressor, hot recycle valve, cold recycle
+ valve, cooler, mixer, recycle blocks, and `ProcessSystem`. It also explains how
+ to **auto-generate a compressor chart with surge and stonewall curves** when no
+ vendor chart is available, because every anti-surge option needs a surge limit
+ to act against.
+ The pure-Python helper (`AntiSurgeRecycleModel`) is an educational planning aid
+ that mirrors NeqSim's proportional anti-surge step so an agent can pre-estimate
+ the recycle flow and decide whether a chart must be generated first. Real
+ control design must use the validated NeqSim equipment classes below and a
+ qualified rotating-equipment review (API 617 / API 692).
+
## When to Use
- - Coordinating compressor speed and recycle-valve opening at minimum speed (e.g. PEPR control optimization)
- - Preventing opposing speed demand and recycle-valve opening in compressor pressure loops
- - Sizing anti-surge recycle valves and modeling anti-surge controllers
- - Calculating power penalties, fuel gas consumption, CO2 emission reductions, and financial cost savings ($CO_2$ tax + fuel gas value) from eliminating unnecessary recycle opening
- - Running dynamic simulation of split-range pressure, speed, and recycle control using `MinimumSpeedRecycleControllerStructure`
+ Use this skill when:
- Standards: **API 617 / API 619**, **IEC 60534 / ISA-75**, **ISO 50001 / ISO 14064** (energy & carbon emissions).
+ - A NeqSim compressor operating point can fall to the left of its surge line at
+ low throughput (turndown, start-up, trips) and needs recycle protection.
+ - You must build the anti-surge recycle topology (surge curve, recycle stream,
+ discharge splitter or recycle branch, anti-surge valve, `Recycle`, and
+ optional cooler/mixer).
+ - You need an executable dynamic application model where
+ `CompressorAntiSurgeApplication` writes hot/cold recycle valve openings and
+ optional compressor speed runback to real NeqSim units.
+ - **No vendor compressor chart is provided** and a chart with surge and
+ stonewall curves must be generated from the compressor's design point.
+ - You want a screening estimate of the recycle flow required to keep the
+ compressor off surge before running the full simulation.
- ## Compressor pressure-target solves
+ Do not use this skill as a substitute for vendor performance maps, anti-surge
+ controller tuning, dynamic surge/transient analysis, or rotating-equipment
+ design review.
+ ## Inputs
+
+ - Compressor inlet (suction) volumetric flow at the operating point (m3/h).
+ - Surge-limit flow at the operating head and speed (m3/h). When no vendor chart
+ is available, this comes from the generated surge curve.
+ - Whether a vendor compressor chart is provided (`chart_provided`).
+ - Existing recycle flow, if any (m3/h).
+ - For chart generation: a design speed, the number of speed lines, and
+ optionally impeller diameter / number of stages for advanced corrections.
+
+ ## Outputs
+
+ - `needs_chart_generation` — whether a chart must be generated before control.
+ - `in_surge` — whether the operating point is at or below the surge flow.
+ - `surge_margin_fraction` — `(inlet_flow - surge_flow) / surge_flow`.
+ - `recommended_recycle_flow` — screening recycle flow to add at suction (m3/h).
+ - `total_suction_flow` — inlet flow plus recommended recycle (m3/h).
+ - `recycle_warning` — `ok`, `recycle`, or `surge`.
+ - Assumptions and limitations.
+
+ ## Engineering Method
+
+ A centrifugal compressor surges when the inlet volumetric flow drops below the
+ surge flow at the current head/speed. Anti-surge control opens a recycle line
+ from discharge back to suction to keep the **total** suction flow above the
+ surge limit plus a margin.
+
+ For steady-state recycle sizing and initialization, prefer
+ `AntiSurgeRecycleCalculator` for a charted compressor. It runs the compressor,
+ checks natural inlet flow against the surge-control line, and iterates a cooled
+ recycle stream until the target distance-to-surge margin is met. Use the older
+ splitter-based `Calculator` / `AntiSurgeCalculator` pattern only when you need
+ to reproduce an existing flowsheet that already uses a discharge splitter.
+
+ The legacy splitter-based topology is:
+
+ 1. A **surge curve** on the compressor chart provides the surge flow versus head.
+ 2. A low-flow **recycle stream** is added into the compressor suction.
+ 3. A **splitter** on the compressor discharge creates a forward branch
+ (`getSplitStream(0)`) and a recycle branch (`getSplitStream(1)`).
+ 4. An **anti-surge `Calculator`** (legacy name-prefix API) or typed
+ `AntiSurgeCalculator` reads the compressor and writes the splitter recycle
+ flow each iteration. Internally it compares the inlet flow to the surge flow:
+ far from surge (`inlet_flow > 1.2 * surge_flow`) it drives recycle to a
+ minimum; otherwise it adds a proportional, capped step
+ `0.5 * (surge_flow - inlet_flow)` to the recycle branch.
+ 5. An **anti-surge valve** on the recycle branch drops the discharge pressure
+ back to suction pressure.
+ 6. A **`Recycle`** unit closes the loop, feeding the valve outlet back into the
+ placeholder suction recycle stream.
+
+ ### Generating a Compressor Chart When None Is Given
+
+ The anti-surge loop needs a surge limit, so if no vendor chart exists a chart
+ must be generated first. NeqSim builds a chart from the compressor's design
+ operating point and **automatically populates both the surge curve and the
+ stonewall curve**:
+
+ - `Compressor.generateCompressorChart("normal curves", numberOfSpeeds)` builds a
+ multi-speed chart whose lowest-flow points form the surge curve and whose
+ highest-flow points form the stonewall curve.
+ - `CompressorChartGenerator` gives finer control (chart type, Reynolds/Mach
+ corrections, multistage surge correction, impeller diameter) and also returns
+ a chart with surge and stonewall curves attached.
+
+ After generation, the surge flow at the operating head is available through
+ `Compressor.getSurgeFlowRate()` and the distance to surge through
+ `Compressor.getDistanceToSurge()`.
+
+ The `AntiSurgeRecycleModel` mirrors step 4 so you can estimate the recycle flow
+ and flag whether chart generation (`needs_chart_generation`) is required before
+ wiring the loop.
+
+ ## Python Usage Pattern
+
+ Screening estimate of the recycle flow (no NeqSim required):
+
+ ```python
+ from compressor_antisurge_recycle import AntiSurgeRecycleModel
+
+ model = AntiSurgeRecycleModel()
+ plan = model.plan(
+ inlet_flow=4200.0, # m3/h at suction
+ surge_flow=5000.0, # m3/h surge limit at operating head
+ chart_provided=True,
+ current_recycle=0.0,
+ )
+ print(plan.recommended_recycle_flow, plan.recycle_warning)
+ ```
+
+ Generate a compressor chart (with surge and stonewall curves) when none is
+ given, using NeqSim through the `neqsim` package:
+
+ ```python
+ from neqsim import jneqsim
+
+ # `compressor` is an existing neqsim.process.equipment.compressor.Compressor
+ compressor.setSpeed(8000.0) # design speed (rpm)
+ compressor.run() # solve the design point first
+ compressor.generateCompressorChart("normal curves", 5) # 5 speed lines
+
+ # Surge and stonewall curves are now populated automatically.
+ chart = compressor.getCompressorChart()
+ surge_flow = compressor.getSurgeFlowRate()
+ distance_to_surge = compressor.getDistanceToSurge()
+ ```
+
+ Finer control with the generator (optional corrections):
+
+ ```python
+ from neqsim import jneqsim
+
+ generator = jneqsim.process.equipment.compressor.CompressorChartGenerator(compressor)
+ generator.setChartType("interpolate and extrapolate")
+ generator.enableAdvancedCorrections(numberOfStages) # Reynolds + Mach + multistage
+ chart = generator.generateCompressorChart("normal curves", 5)
+ compressor.setCompressorChart(chart)
+ ```
+
+ Wire the anti-surge recycle loop (generic data, after a chart exists):
+
+ ```python
+ from neqsim import jneqsim
+
+ splitter_pkg = jneqsim.process.equipment.splitter
+ valve_pkg = jneqsim.process.equipment.valve
+ util_pkg = jneqsim.process.equipment.util
+
+ suction_pressure = compressor.getInletStream().getPressure("bara")
+
+ # 2. Low-flow placeholder recycle stream into the compressor suction.
+ recycle_gas = compressor.getInletStream().clone()
+ recycle_gas.setName("anti surge recycle gas")
+ recycle_gas.setFlowRate(1.0, "kg/hr")
+ recycle_gas.run()
+ process.add(recycle_gas)
+
+ # 3. Splitter on the compressor discharge: branch 0 forward, branch 1 recycle.
+ gas_splitter = splitter_pkg.Splitter("anti surge splitter", compressor.getOutletStream(), 2)
+ gas_splitter.run()
+ process.add(gas_splitter)
+
+ # 4. Anti-surge Calculator (name MUST start with "anti surge calculator").
+ anti_surge_calc = util_pkg.Calculator("anti surge calculator 1")
+ anti_surge_calc.addInputVariable(compressor)
+ anti_surge_calc.setOutputVariable(gas_splitter)
+ process.add(anti_surge_calc)
+
+ # 5. Anti-surge valve on the recycle branch back to suction pressure.
+ anti_surge_valve = valve_pkg.ThrottlingValve("anti surge valve", gas_splitter.getSplitStream(1))
+ anti_surge_valve.setOutletPressure(suction_pressure, "bara")
+ anti_surge_valve.run()
+ process.add(anti_surge_valve)
+
+ # 6. Recycle unit closes the loop into the placeholder suction stream.
+ recycle = util_pkg.Recycle("recycle anti surge")
+ recycle.addStream(anti_surge_valve.getOutletStream())
+ recycle.setOutletStream(recycle_gas)
+ recycle.setTolerance(1e-2)
+ process.add(recycle)
+
+ process.run()
+ ```
+
+ The forward process continues on `gas_splitter.getSplitStream(0)`.
+
+ Preferred steady-state helper for a charted compressor:
+
+ ```java
+ AntiSurgeRecycleCalculator calc = new AntiSurgeRecycleCalculator(compressor, suctionStream);
+ calc.setSurgeControlMargin(0.10);
+ calc.setRecycleCoolerTemperature(35.0, "C");
+ AntiSurgeRecycleCalculator.Result result = calc.solve();
+ ```
+
+ ## Dynamic Anti-Surge Control (AntiSurgeController)
+
+ The `Calculator`-driven loop above is a **steady-state** recycle solver. For a
+ **dynamic (transient)** anti-surge response, NeqSim provides a dedicated
+ reverse-acting PI controller, `AntiSurgeController`
+ (`neqsim.process.controllerdevice.AntiSurgeController`), that reads
+ `Compressor.getDistanceToSurge()` and drives a recycle `ThrottlingValve` open as
+ the margin falls below the set point, then closes it again on recovery.
+
+ ```python
+ from neqsim import jneqsim
+
+ controllerdevice = jneqsim.process.controllerdevice
+
+ # `recycle_valve` is the anti-surge ThrottlingValve on the recycle branch.
+ asc = controllerdevice.AntiSurgeController("anti-surge", compressor, recycle_valve)
+ asc.setSurgeMarginSetPoint(0.10) # protect a 10% distance-to-surge margin
+ asc.setProportionalGain(400.0) # percent opening per unit margin error
+ asc.setIntegralTime(20.0) # s
+ asc.setOpeningRange(0.0, 100.0) # valve opening clamp (%) with anti-windup
+ asc.setActive(True)
+ recycle_valve.addController("anti-surge", asc)
+ ```
+
+ Control law each transient step: `error = setPoint - distanceToSurge`,
+ `integral += Kp/Ti * error * dt`, `opening = clamp(Kp*error + integral)` with
+ anti-windup. A reproducible benchmark,
+ `neqsim.process.util.scenario.AntiSurgeDynamicBenchmark`, drives the real
+ controller against a transparent first-order gas-path surrogate
+ (`m_next = m - disturbance*dt + authority*(opening/100)*dt`) and is the preferred
+ way to verify or tune the control law without solver fragility.
+
+ **Critical gotchas when building a full dynamic recycle flowsheet:**
+
+ - A fixed-factor `Splitter` (`setSplitFactors([0.97, 0.03])`) **pins the recycle
+ fraction** in dynamic mode, so the anti-surge valve has no authority over the
+ actual recycle flow — it can reach 100% open with no effect. Let the recycle
+ flow be set by the valve (`Cv`/resistance), or keep the steady-state
+ `Calculator` pattern.
+ - Once the operating point crosses left of the surge line,
+ `getDistanceToSurge()` **clamps at -1.0 and the steady solver cannot recover**;
+ a flowsheet driven into deep surge will not self-heal even after the inlet is
+ reopened. Apply gradual/ramped disturbances and keep the machine off deep surge.
+ - Aggressive proportional gain can slam the recycle valve to minimum opening,
+ starve a stream, and trigger an SRK flash `NaN`
+ (`PhaseSrkEos:molarVolume ... NaN`). Keep gains moderate.
+
+ Dynamic controller tuning and transient surge analysis still require qualified
+ rotating-equipment review (API 617 / API 692).
+
+ ## Application-Level Dynamic Topology Binding
+
+ For realistic dynamic studies with coordinated pressure, speed, hot recycle, and
+ cold recycle behavior, use `CompressorAntiSurgeApplication`. It is a
+ deterministic supervisory scan layer that can write directly to real NeqSim
+ objects and then advance the bound process one transient step.
+
+ ```java
+ CompressorAntiSurgeApplication application = new CompressorAntiSurgeApplication("export compression");
+ CompressorAntiSurgeApplication.StageApplication stage = application.addStage("K-101");
+
+ CompressorAntiSurgeApplication.TopologyBinding binding = stage.bindTopology(
+ process,
+ compressor,
+ hotRecycleValve,
+ coldRecycleValve,
+ recycleCooler,
+ suctionMixer,
+ hotRecycle,
+ coldRecycle);
+ binding.enableSpeedControl(95.0, 25.0, 8500.0, 12500.0, 150.0);
+
+ application.setRunningMode();
+ application.runDynamicStep(null, 0.25);
+ ```
+
+ When the scan input is `null`, the stage reads the bound compressor margin and
+ inlet flow where available, falls back to the stage design basis where needed,
+ writes the hot and cold recycle valve openings, applies the optional compressor
+ speed command/runback, and advances the bound `ProcessSystem` with
+ `runTransient()`. Keep `Recycle` blocks algebraic unless the specific class has
+ transient inventory support; the valve, compressor, cooler, mixer, and any
+ volume-capable equipment carry the dynamic response.
+
+ `CompressorAntiSurgeApplication` is still a simulation and advisory layer. Its
+ certification status remains `NOT_CERTIFIED_FOR_PROTECTION`; use it for
+ engineering studies, training, digital twins, and commissioning evidence, not as
+ a certified machinery-protection package.
+
+ ## MCP `runProcess` Physical Topology Contract
+
+ Use two distinct JSON surfaces deliberately:
+
+ - Compressor property `antiSurge` configures the compressor's embedded
+ screening control. It does not create or certify a physical recycle path.
+ - Root-level `antiSurgeSystems` binds
+ `CompressorAntiSurgeApplication` to named units that already exist in the
+ submitted `process` topology. It never synthesizes hidden valves, coolers,
+ mixers, or recycle blocks.
+
+ A single-area cold-recycle declaration has this shape:
+
+ ```json
+ {
+ "autoSizing": {"enabled": true},
+ "antiSurgeSystems": [
+ {
+ "name": "Export anti-surge",
+ "stages": [
+ {
+ "name": "Stage 1",
+ "compressor": "Comp",
+ "suctionMixer": "Suction Mixer",
+ "aftercooler": "Aftercooler",
+ "coldRecycleValve": "Cold ASV",
+ "coldRecycle": "Cold Recycle",
+ "recycleDesign": {
+ "controlMargin": 0.10,
+ "valvePressureDrop": 10.0,
+ "pipingVolume": 1.0,
+ "requiredResponseTime": 5.0
+ },
+ "speedControl": {
+ "dischargePressureSetPoint": 40.0,
+ "minimumSpeed": 5000.0,
+ "maximumSpeed": 15000.0,
+ "speedGain": 40.0,
+ "recycleRunbackRate": 80.0
+ }
+ }
+ ]
+ }
+ ]
+ }
+ ```
+
+ The referenced names must resolve to the expected concrete types:
+ `Compressor`, `Mixer`, optional `Cooler`, `ThrottlingValve`, and `Recycle`.
+ At least one complete hot or cold recycle path is required. For a multi-area
+ `ProcessModel`, every system also requires an `area` matching a submitted area;
+ unqualified and unknown-area definitions return bounded per-system failures.
+
+ Every stage needs an active surge curve. Supply `properties.compressorChart`,
+ enable `autoSizing`, or set `generateScreeningMap: true` on the stage. The
+ response reports truthful map provenance:
+
+ - `submitted`: chart was present in the submitted canonical process JSON.
+ - `auto_sized_screening`: `autoSizing` generated the chart earlier in the run.
+ - `stage_generated_screening`: the anti-surge stage generated the chart.
+
+ The latter two set `screeningGradeMap: true`. They are estimates, not vendor
+ maps. `generatedScreeningMapCount` counts all configured stages using a
+ screening-grade map, regardless of which generation path created it.
+
+ The response `antiSurgeSystems` object contains configured/failed counts,
+ per-stage physical binding and map provenance, optional speed-control status,
+ and `runCommissioningChecks()` evidence. Its certification status is always
+ `NOT_CERTIFIED_FOR_PROTECTION`. The canonical `processDefinition` preserves the
+ declaration, and the generated Python replays that canonical post-design JSON.
+
+ When a canonical response is replayed, its exported compressor chart is now an
+ explicitly submitted chart for that new request. Therefore its provenance is
+ `submitted`; replay does not generate another map. This makes JSON round trips
+ stable while preserving the original run's generation evidence in that run's
+ response.
+
+ ## Compressor Pressure-Target Solves
+
For `Compressor.setSolveSpeed(true)`, check `isSpeedSolveConverged()` after `run()`
before accepting an optimization point. Read actual pressure from the outlet
stream and the signed pressure error in bar from `getSpeedSolvePressureResidual()`.
`getOutletPressure()` retains the requested setpoint, including after failure.
The returned state uses the fixed-speed forward calculation, including anti-surge
flow changes; these can leave the requested pressure unmet. `setLimitSpeed(false)`
allows extrapolation, so pressure convergence does not establish mechanical
feasibility. Check speed and operating-envelope constraints separately.
`ProductionOptimizer` treats `Compressor.SpeedSolveException` as an infeasible
trial and continues searching without evaluating stale outputs; unrelated
exceptions propagate. Its hard `compressorSpeedSolve` constraint also rejects
returned unconverged results even with capacity analysis enabled. Keep this gate
- when integrating chart-based compressor models into optimizers.
- See [compressor curves](../../../docs/process/equipment/compressor_curves.md#speed-calculation-from-operating-point)
+ when integrating chart-based compressor models into optimizers. See the
+ [compressor curves guide](https://equinor.github.io/neqsim/process/equipment/compressor_curves.html)
and `CompressorSpeedSolveConsistencyTest` for the tested contract.
- ## Key Java Class: `MinimumSpeedRecycleControllerStructure`
-
- `neqsim.process.controllerdevice.structure.MinimumSpeedRecycleControllerStructure` coordinates pressure control between compressor speed and recycle-valve opening when the compressor reaches its minimum speed.
-
- ### Core Features
+ ## Minimum-Speed Recycle Coordination (`MinimumSpeedRecycleControllerStructure`)
- 1. **Split-Range Output Transition**: Pressure controller output is divided at a configurable transition (e.g., 75%).
- 2. **Speed Command Range**: Above transition (75% to 105%), recycle addition is zero and compressor speed increases linearly from minimum (75%) to maximum (100%).
- 3. **Inverse Recycle Addition**: Below transition (0% to 75%), speed is held at minimum (75%) while an inverse recycle addition increases as pressure output falls.
- 4. **Latch on Entry**: On lower-range entry, the previously selected recycle command is latched and pressure-derived recycle is added to that baseline.
- 5. **High Selector Protection**: Independent anti-surge and suction-pressure demands participate in a high selector ($R_{selected} = \max(R_{latch} + R_{add}, R_{AS}, R_{suction})$) so protection authority is never suppressed.
- 6. **Unwind before Speed Increase**: On rising pressure, pressure-derived recycle unwinds to the latched baseline before speed increases.
- 7. **Dynamic Saturation Floor**: Applies a lower output limit (`latched * 74 / 100`) to prevent integral windup.
+ `neqsim.process.controllerdevice.structure.MinimumSpeedRecycleControllerStructure`
+ coordinates pressure control between compressor speed and recycle-valve opening when
+ the compressor reaches its minimum speed. Use it to stop opposing speed demand and
+ recycle-valve opening in a compressor pressure loop (control-optimization tasks).
- ### Java Usage Pattern
+ 1. **Split-range output:** the pressure controller output is divided at a configurable
+ transition (e.g. 75 %).
+ 2. **Speed command range:** above the transition (75 % to 105 %) recycle addition is
+ zero and speed rises linearly from minimum (75 %) to maximum (100 %).
+ 3. **Inverse recycle addition:** below the transition (0 % to 75 %) speed is held at
+ minimum while recycle addition increases as pressure output falls.
+ 4. **Latch on entry:** on lower-range entry the previously selected recycle command is
+ latched and pressure-derived recycle is added to that baseline.
+ 5. **High-selector protection:** independent anti-surge and suction-pressure demands
+ join a high selector, $R_{selected} = \max(R_{latch} + R_{add}, R_{AS}, R_{suction})$,
+ so protection authority is never suppressed.
+ 6. **Unwind before speed increase:** on rising pressure, pressure-derived recycle
+ unwinds to the latched baseline before speed increases.
+ 7. **Dynamic saturation floor:** a lower output limit (`latched * 74 / 100`) prevents
+ integral windup.
```java
import neqsim.process.controllerdevice.ControllerDeviceInterface;
import neqsim.process.controllerdevice.ControllerDeviceBaseClass;
import neqsim.process.controllerdevice.structure.MinimumSpeedRecycleControllerStructure;
- // Create controllers
ControllerDeviceInterface pressureController = new ControllerDeviceBaseClass("PIC-0205A");
ControllerDeviceInterface antiSurgeController = new ControllerDeviceBaseClass("UIC-0231");
ControllerDeviceInterface suctionController = new ControllerDeviceBaseClass("PIC-0131");
- // Instantiate structure: (pressureCtrl, antiSurgeCtrl, suctionCtrl, transitionPct, maxOutputPct, minSpeedPct, maxSpeedPct)
+ // (pressureCtrl, antiSurgeCtrl, suctionCtrl, transitionPct, maxOutputPct, minSpeedPct, maxSpeedPct)
MinimumSpeedRecycleControllerStructure coordStructure = new MinimumSpeedRecycleControllerStructure(
- pressureController, antiSurgeController, suctionController, 75.0, 105.0, 75.0, 100.0
- );
+ pressureController, antiSurgeController, suctionController, 75.0, 105.0, 75.0, 100.0);
- // In transient loop or update step:
+ // In the transient loop or update step:
coordStructure.update(pressureControllerOutput, antiSurgeOutput, suctionPressureOutput);
double speedCommand = coordStructure.getSpeedOutput(); // % speed
- double recycleAddition = coordStructure.getRecycleAddition(); // % recycle addition
- double recycleCommand = coordStructure.getLatchedRecycleOutput(); // % latched baseline
+ double recycleAddition = coordStructure.getRecycleAddition(); // % recycle addition
+ double recycleCommand = coordStructure.getLatchedRecycleOutput(); // % latched baseline
```
- ## Energy & CO2 Savings Quantification Pattern
+ ## Energy and CO2 Savings from Avoided Recycle
- When recycle opens uncoordinatedly while the compressor is operating at minimum or elevated speed, extra gas is re-compressed without increasing net forward production.
+ When recycle opens uncoordinatedly while the compressor runs at minimum or elevated
+ speed, extra gas is re-compressed without increasing net forward production.
- ### Governing Equations
+ 1. Shaft power: $P_{shaft} = \dfrac{\dot{m}_{net}\, h_{poly}}{\eta_p (1 - \alpha_{recycle})}$,
+ with recycle fraction $0 \le \alpha < 1$.
+ 2. Power penalty: $\Delta P = P_0\,\dfrac{\alpha}{1 - \alpha}$.
+ 3. Fuel and CO2: $\Delta \dot{m}_{fuel} = \dfrac{\Delta P}{\eta_{driver}\,LHV}$ and
+ $\Delta \dot{m}_{CO2} = \Delta \dot{m}_{fuel}\, e_{CO2}$.
+ 4. Annual saving (MNOK/yr) $= \dfrac{\Delta m_{CO2,yr}\,\mathrm{Tax}_{CO2} + \Delta m_{fuel,yr}\,\mathrm{Value}_{gas}}{10^6}$.
- 1. **Compressor Shaft Power**:
- $$P_{shaft} = \frac{\dot{m}_{total} \cdot h_{poly}}{\eta_p} = \frac{\dot{m}_{net} \cdot h_{poly}}{\eta_p (1 - \alpha_{recycle})}$$
- where $\alpha_{recycle}$ is the recycle fraction ($0 \le \alpha < 1$).
+ Recipe: build the recompressor with a fixed net feed, then sweep the recycle fraction
+ by setting the suction flow to `net / (1 - alpha)` and re-running stream and compressor;
+ the power difference to $\alpha = 0$ is the penalty. Quantify annual MWh, fuel-gas
+ tonnes, CO2 tonnes and cost over the operating hours, and compare the dynamic
+ pressure, speed, recycle, power and CO2 time series.
- 2. **Power Penalty**:
- $$\Delta P = P_{shaft}(\alpha) - P_{shaft}(0) = P_0 \left(\frac{\alpha}{1 - \alpha}\right)$$
+ ## Fixed Minimum Flow Without a Numerical Recycle Loop
- 3. **Fuel Gas & CO2 Emission Penalty**:
- $$\Delta \dot{m}_{fuel} = \frac{\Delta P}{\eta_{driver} \cdot LHV} \quad (\text{kg/hr})$$
- $$\Delta \dot{m}_{CO2} = \Delta \dot{m}_{fuel} \cdot e_{CO2} \quad (\text{kg } CO_2/\text{hr})$$
+ For steady-state screening with a prescribed minimum suction flow and a return cooled
+ to the net-feed suction state, use
+ `neqsim.process.equipment.compressor.MinimumFlowSpill(name, netFeed)`.
+ Set `setMinimumInletFlow(value, unit)` and configure `getCompressor()`.
+ Add the assembly once to the `ProcessSystem`; the net forward outlet is
+ `getOutletStream()`, while `getSpillStream()` is an internal discharge spill.
+ `getSpillFlow(unit)` uses suction conditions even for actual volume.
+ Use `getPower(unit)` for gross compression and `getSpillCoolingDuty(unit)` for
+ ideal heat rejection. The assembly delegates capacity constraints to its compressor.
+ Disable internal AntiSurge flow modification. Use physical valve, cooler and recycle
+ equipment for composition changes, condensation, finite cooler approach or dynamics.
+ See the [compressor equipment guide](https://equinor.github.io/neqsim/process/equipment/compressors.html)
+ and `MinimumFlowSpillTest` for the executed synthetic material and energy checks.
- 4. **Financial Cost Savings**:
- $$\text{Annual Savings (MNOK/yr)} = \frac{\Delta m_{CO2, yr} \cdot \text{Tax}_{CO2} + \Delta m_{fuel, yr} \cdot \text{Value}_{gas}}{10^6}$$
+ ## Validation Checklist
- ### Python / NeqSim Process Simulation Recipe
+ - The compressor has a chart with an active surge curve before the loop runs;
+ if not, generate one and confirm `getSurgeCurve().isActive()` is true.
+ - For steady-state recycle initialization, use `AntiSurgeRecycleCalculator` when
+ practical; if using the legacy splitter path, the anti-surge `Calculator` name
+ starts with `"anti surge calculator"` or the typed `AntiSurgeCalculator` is
+ used.
+ - For the legacy splitter path, the `Calculator` input is the `Compressor` and
+ the output is the discharge `Splitter`.
+ - The anti-surge valve sits on `getSplitStream(1)` and drops to suction pressure.
+ - The `Recycle` outlet stream is the placeholder suction recycle stream.
+ - After `process.run()`, the total suction flow exceeds the surge flow plus the
+ intended margin (`getDistanceToSurge()` is positive).
+ - Recycle convergence tolerance is set (for example `setTolerance(1e-2)`).
+ - For `CompressorAntiSurgeApplication` topology binding, hot/cold recycle valves
+ are real `ThrottlingValve` units, speed-control limits are bounded, and
+ `runDynamicStep(...)` is used only after the process has a converged initial
+ state.
+ - For MCP `runProcess`, use root-level `antiSurgeSystems` only after all named
+ physical units are present in `process`; require `area` for every multi-area
+ system and inspect `configuredCount`, `failedCount`, `mapProvenance`,
+ `screeningGradeMap`, commissioning checks, and certification status.
+ ## Common Mistakes
+
+ - Naming the legacy calculator anything that does not start with
+ `"anti surge calculator"` — the legacy anti-surge logic then never triggers.
+ - Wiring the anti-surge valve to the forward branch `getSplitStream(0)` instead
+ of the recycle branch `getSplitStream(1)`.
+ - Running the loop without a surge curve, so there is no surge flow to compare
+ against (generate a chart first when no vendor chart is given).
+ - Using a zero or negative placeholder recycle flow that the `Recycle` cannot
+ converge from; start from a small positive flow (for example 1 kg/hr).
+ - Reading the surge flow at the wrong head or speed — the surge flow must match
+ the operating head and speed.
+ - Treating the generated chart as a vendor-validated map; generated charts are
+ estimates for modelling, not design certification.
+ - For dynamic studies, leaving a fixed-factor `Splitter` on the recycle branch so
+ the `AntiSurgeController` valve has no authority over the recycle flow.
+ - Driving a dynamic recycle flowsheet straight into deep surge, where
+ `getDistanceToSurge()` clamps at -1.0 and the steady solver cannot recover.
+ - Loading a VENDOR map into the default chart. `Compressor`'s default `"fan law"`
+ `CompressorChart` fits one quadratic of H/N^2 vs Q/N through all speed lines,
+ which on a real vendor map shifts discharge pressure by 10-15 % at the outer
+ speed lines (and moves the surge flow with it). Call
+ `compressor.setCompressorChartType("interpolate and extrapolate")` BEFORE
+ `getCompressorChart().setCurves(...)`; `Pump.setPumpChartType(...)` has the same
+ option. Units for `setCurves`: actual inlet m3/hr, head `kJ/kg` or `meter`,
+ polytropic efficiency in PERCENT.
+ - Checking anti-surge valve capacity with the default `ThrottlingValve` sizing.
+ The default method uses xT = 0.137 without choking and under-rates a globe
+ anti-surge valve by a factor ~2 at pressure ratio 4. Set
+ `getMechanicalDesign().setValveSizingStandard("IEC 60534")`, then on
+ `getValveSizingMethod()` call `setxT(0.70)`, `setFL(0.90)` (or the vendor's
+ values) and `setAllowChoked(True)` before `setCv(cv, "US")`.
+ - Setting the control-line margin from habit instead of the machine's anti-surge
+ write-up. Vendor controllers store the surge-control line as a function
+ generator in (Q^2, DP/Ps) coordinates; the flow margin is
+ sqrt(Q^2_SCL / Q^2_SLL) - 1 at equal DP/Ps (~20 % in Q^2 = ~10 % in flow is
+ typical), then `compressor.setSurgeControlMargin(margin)`.
+
+ ## Limitations
+
+ - Screening logic only; it does not tune an anti-surge controller or set
+ recycle valve `Cv`, response time, or surge control line offset.
+ - The Python helper does not perform dynamic surge, ESD, or transient recycle
+ analysis; for dynamic response use NeqSim's `AntiSurgeController` /
+ `AntiSurgeDynamicBenchmark` under qualified review.
+ - Generated compressor charts are model estimates, not vendor performance maps.
+ - It does not replace API 617 / API 692 rotating-equipment design and review.
+ - Results require qualified human review before any design or operating use.
+
+ ## Multi-Body Compressor Trains on One Shaft (common speed)
+
+ When several compressor bodies sit on **one driver shaft** (a single gas turbine
+ or motor, often through a gearbox) they must all turn at the **same speed**. A
+ 2- or 3-body recompression string is the classic case. Model it with
+ `neqsim.process.equipment.compressor.CompressorShaft`, NOT by letting each body
+ solve its own speed.
+
+ **Degrees of freedom.** A shared shaft has exactly **one** mechanical degree of
+ freedom — the common speed — and exactly **one** controlled target: the string's
+ **final discharge pressure**. Every intermediate inter-body pressure is a
+ *result*, not a spec, and must be allowed to **float** off the charts.
+
+ | Approach | DOF accounting | Verdict |
+ |---|---|---|
+ | Fix every stage outlet pressure **and** set a common speed | over-constrained | ❌ non-physical |
+ | Adjust ONE common speed → hit the final discharge; intermediates float | 1 variable, 1 target | ✅ correct |
+
+ **Pattern.** Put each body in fixed-speed, chart-forward mode and iterate the one
+ common speed until the reference (last) body hits the target discharge:
+
```python
- from neqsim import jneqsim
+ CompressorShaft = jneqsim.process.equipment.compressor.CompressorShaft
+ shaft = CompressorShaft("recompression shaft (single GT)")
+ shaft.addCompressor(body1) # LP body (lowest suction)
+ shaft.addCompressor(body2)
+ shaft.addCompressor(body3) # HP body = reference
+ shaft.setSpeedBounds(8000.0, 16000.0)
+ # re-run the whole flowsheet between speed guesses so inter-body streams,
+ # scrubbers and mixers update:
+ run_proxy = jpype.JProxy("java.lang.Runnable", dict(run=lambda: process.run()))
+ shaft.solveSpeed(body3, 49.0, "bara", run_proxy) # one speed -> 49 bara at HP discharge
+ rpm = shaft.getSpeed()
+ mw = shaft.getTotalPower() / 1e6
+ ```
- # 1. Fluid Creation
- fluid = jneqsim.thermo.system.SystemSrkEos(311.15, 12.5) # 38 °C, 12.5 bara
- fluid.addComponent("methane", 0.78)
- fluid.addComponent("ethane", 0.085)
- fluid.addComponent("propane", 0.045)
- fluid.addComponent("CO2", 0.040)
- fluid.setMixingRule("classic")
+ **Shared pressure nodes.** Where another unit ties into an interstage (e.g. a
+ 2nd-stage separator gas that joins the recompressor between bodies), model it as
+ a **pressure equality**, not a second spec: slave that unit's pressure to the
+ floating interstage discharge (a setter each iteration) or drop a small adapting
+ valve there. This removes a DOF rather than adding one. A `Mixer` at the join
+ already resolves to the lowest inlet pressure, so a small let-down is automatic.
- # 2. Recompressor Model
- stream = jneqsim.process.equipment.stream.Stream("Suction Gas", fluid)
- stream.setFlowRate(150000.0, "kg/hr") # 150 t/h net flow
- stream.run()
+ **Fixed-/single-speed drivers.** If the driver is a constant-speed motor (no
+ variable-speed drive) speed is **not** a DOF — do **not** iterate it. Use
+ `shaft.runAtFixedSpeed(rpm, run_proxy)`: the discharge floats off the chart at
+ the locked speed and any pressure spec is met by anti-surge recycle, suction
+ throttling, or inlet guide vanes — never by moving speed. Inlet guide vanes are a
+ **first-class** fixed-speed control on `Compressor`:
+ `comp.setInletGuideVaneOpening(f)` (`f=1` fully open) or `comp.setGuideVaneAngle(deg)`
+ closes the vanes to reduce head and efficiency **and** lower the surge flow (via a
+ configurable `InletGuideVaneModel`), so `getDistanceToSurge()` reflects the shifted
+ surge line — distinct from moving speed. If you have vendor **IGV-position** maps
+ (a full chart per vane position), attach a `CompressorChartIGV` family with
+ `comp.setInletGuideVaneChart(family)`; it interpolates the positions into the active
+ chart at each opening (and bypasses the parametric model). Use the parametric
+ `InletGuideVaneModel` for screening / fixed-speed discharge control, and
+ `CompressorChartIGV` to supply real per-position vendor maps.
- comp = jneqsim.process.equipment.compressor.Compressor("Recompressor", stream)
- comp.setOutletPressure(45.0, "bara")
- comp.setPolytropicEfficiency(0.78)
- comp.setUsePolytropicCalc(True)
- comp.run()
+ **Single body.** A `CompressorShaft` with one compressor also works: `solveSpeed`
+ just finds that one machine's speed for its discharge target. So export /
+ re-injection / gas-lift machines (one body each on their own shaft) use the same
+ API — separate shafts keep separate speeds.
- base_power_kw = comp.getPower() / 1000.0
+ **Anti-surge coexists.** The per-body anti-surge loops (recycle splitter, valve,
+ `Recycle`, `AntiSurgeCalculator`) stay attached and keep protecting each body;
+ they adjust *recycle flow*, while the shaft sets *speed*. Apply the shaft solve
+ **after** the charts and anti-surge are active. `solveSpeed` uses a bracketed
+ false-position (Illinois) secant — the speed↔discharge map is smooth and
+ monotonic (higher speed → higher discharge), so it converges superlinearly. Each
+ iteration re-solves the whole flowsheet, so on a large multi-train plant make the
+ shaft solve **opt-in** and solve each train's shaft in turn.
- # 3. Recycle Sweep
- for r_frac in [0.0, 0.10, 0.20, 0.30]:
- total_flow = 150000.0 / (1.0 - r_frac)
- stream.setFlowRate(total_flow, "kg/hr")
- stream.run()
- comp.run()
- p_kw = comp.getPower() / 1000.0
- extra_kw = p_kw - base_power_kw
- extra_co2_t_hr = (extra_kw / (0.34 * 48000.0)) * 3600.0 * 2.75 / 1000.0
- print(f"Recycle {r_frac*100:.0f}%: Power = {p_kw:.1f} kW (+{extra_kw:.1f} kW), Extra CO2 = +{extra_co2_t_hr:.2f} t/h")
+ **Parallel machines and multi-stage strings.** Real duties often use two parallel
+ bodies (A/B) rather than one machine: split the feed 50/50, give each body its own
+ anti-surge loop, and commingle with a `Mixer`. Splitting one large machine into two
+ halves the per-machine gas load (a suction scrubber that reads ~168 % of design on
+ one body drops to ~80 % on two). For a multi-stage duty (e.g. re-injection),
+ commingle the parallel 1st-stage discharges then feed a common 2nd stage at an
+ interstage pressure. Route a recompression train's HP discharge back to the gas
+ header, not straight into the export suction.
+
+ **Process-integrated control (`CompressorShaftCalculator`).** Instead of the
+ external `solveSpeed` callback, add a `CompressorShaftCalculator` to the
+ `ProcessSystem`; it converges the one common speed **inside** `process.run()`
+ (one damped secant step per pass, like `AntiSurgeCalculator`) so the shaft speed
+ converges together with the recycles in a single run — no separate full-field
+ solves. Add it **after** the compressor bodies / anti-surge.
+
+ ```python
+ CompressorShaftCalculator = jneqsim.process.equipment.util.CompressorShaftCalculator
+ shaft = CompressorShaft("recompression shaft (single GT)")
+ shaft.addCompressor(body1); shaft.addCompressor(body2); shaft.addCompressor(body3)
+ shaftCalc = CompressorShaftCalculator("shaft speed", shaft, body3, 49.0, "bara")
+ shaftCalc.setSpeedBounds(8000.0, 16000.0)
+ process.add(shaftCalc)
+ process.run() # shaft speed converges with the recycles
+ rpm = shaftCalc.getSpeed()
```
- ## Checklist for PEPR & Control Optimization Tasks
+ **Feasibility result + pressure control (eCalc-style).** A single-speed string
+ cannot make an arbitrary pressure — the max-speed curve is a ceiling and the
+ min-speed curve is a floor. Both solvers **saturate and flag** instead of
+ crashing, and expose a `CompressorShaft.SolveResult` (read with
+ `getLastSolveResult()`, or the shortcut `isFeasible()`). The two speed-bound
+ bracket evaluations give the **min-/max-achievable** discharge pressures for free.
- - [ ] Verify fluid composition, suction temperature, and pressure basis
- - [ ] Confirm compressor polytropic efficiency, pressure ratio, and head
- - [ ] Model net forward flow vs recycle flow
- - [ ] Calculate shaft power, driver fuel gas rate, and CO2 emissions rate
- - [ ] Benchmark split-range mapping with `MinimumSpeedRecycleControllerStructure`
- - [ ] Quantify annual MWh, fuel gas tonnes, CO2 tonnes, and MNOK cost savings across operating hours
- - [ ] Generate dynamic time-series comparison plots (Pressure, Speed, Recycle, Power & CO2)
+ ```python
+ shaft.solveSpeed(body3, 49.0, "bara", run_proxy)
+ r = shaft.getLastSolveResult()
+ if not r.isFeasible():
+ # r.getStatus(): PRESSURE_ABOVE_MAX_SPEED / PRESSURE_BELOW_MIN_SPEED / OVER_POWER / STONEWALL / SURGE
+ ceiling = r.getMaxAchievablePressure() # most the string can make
+ # too-low target -> shed the surplus head instead of flagging infeasible:
+ PressureControl = jneqsim.process.equipment.compressor.CompressorShaft.PressureControl
+ shaft.setPressureControl(PressureControl.DOWNSTREAM_CHOKE) # or UPSTREAM_CHOKE / ASV_RECYCLE
+ ```
- ## Fixed minimum flow without a numerical recycle loop
+ `CompressorShaftCalculator` carries the same `getLastSolveResult()` /
+ `isFeasible()` / `setPressureControl(...)`, so an optimizer or `evaluate()` loop
+ can gate on `shaftCalc.isFeasible()` directly. Downstream, `Mixer.isPressureMismatch()`
+ flags where an unmet pressure collapses a commingling node to the lowest inlet —
+ the signal that an upstream machine missed spec. A worked end-to-end example
+ (three-stage separation + shared-shaft recompression + control) is in the NeqSim
+ repo notebook `examples/notebooks/CompressorShaft_ThreeStageSeparation.ipynb`.
- For steady-state screening with a prescribed minimum suction flow and a return
- cooled to the net-feed suction state, use
- `neqsim.process.equipment.compressor.MinimumFlowSpill(name, netFeed)`.
- Set `setMinimumInletFlow(value, unit)` and configure `getCompressor()`.
- Add the assembly once to ProcessSystem; the net forward outlet is
- `getOutletStream()`, while `getSpillStream()` is an internal discharge spill.
- `getSpillFlow(unit)` uses suction conditions even for actual volume.
- Use `getPower(unit)` for gross compression and `getSpillCoolingDuty(unit)` for
- ideal heat rejection. The assembly delegates capacity constraints to its compressor.
- Disable internal AntiSurge flow modification. Use physical valve/cooler/recycle
- equipment for composition changes, condensation, finite cooler approach or dynamics.
- See [compressor equipment guide](../../../docs/process/equipment/compressors.md#algebraic-minimum-flow-spill)
- and `MinimumFlowSpillTest` for the executed synthetic material/energy checks.
+ ## Related NeqSim Functionality
+
+ - `neqsim.process.equipment.compressor.CompressorShaft` — groups several
+ compressor bodies on one shaft at a single common speed;
+ `addCompressor(...)`, `solveSpeed(reference, targetP, unit, runnable)` (iterate
+ one speed to the final discharge, intermediates float),
+ `runAtFixedSpeed(rpm, runnable)` (constant-speed drivers), `setSpeed(...)`,
+ `setSpeedBounds(...)`, `getSpeed()`, `getTotalPower()`.
+ - `neqsim.process.equipment.compressor.Compressor` —
+ `generateCompressorChart(...)`, `getCompressorChart()`,
+ `getSurgeFlowRate()`, `getDistanceToSurge()`, `setSpeed(...)`.
+ - `neqsim.process.equipment.compressor.CompressorChart` —
+ `getSurgeCurve()`, `getStoneWallCurve()`, `generateSurgeCurve()`,
+ `generateStoneWallCurve()`, `checkStoneWall(...)`.
+ - `neqsim.process.equipment.compressor.CompressorChartGenerator` —
+ `setChartType(...)`, `enableAdvancedCorrections(...)`,
+ `generateCompressorChart(...)`.
+ - `neqsim.process.equipment.compressor.AntiSurgeRecycleCalculator` — preferred
+ steady-state recycle helper for charted compressors
+ (`setSurgeControlMargin`, `setRecycleCoolerTemperature`, `solve`).
+ - `neqsim.process.equipment.compressor.CompressorAntiSurgeApplication` —
+ application-level supervisor with `StageApplication.bindTopology(...)`,
+ `TopologyBinding.enableSpeedControl(...)`, `scan(...)`, and
+ `runDynamicStep(...)` for direct writeback to real hot/cold recycle valves and
+ compressor speed.
+ - `neqsim.process.equipment.splitter.Splitter` — discharge split into forward
+ and recycle branches.
+ - `neqsim.process.equipment.util.Calculator` — steady-state anti-surge engine
+ (`runAntiSurgeCalc`) triggered by the `"anti surge calculator"` name prefix.
+ - `neqsim.process.controllerdevice.AntiSurgeController` — dynamic reverse-acting
+ PI controller on `getDistanceToSurge()` driving a recycle valve
+ (`setSurgeMarginSetPoint`, `setProportionalGain`, `setIntegralTime`,
+ `setOpeningRange`, `setActive`).
+ - `neqsim.process.util.scenario.AntiSurgeDynamicBenchmark` — reproducible
+ surrogate benchmark for verifying/tuning the dynamic control law.
+ - `neqsim.process.equipment.valve.ThrottlingValve` — anti-surge recycle valve.
+ - `neqsim.process.equipment.util.Recycle` — closes the recycle loop.
+
+ The `total_suction_flow` (net forward flow + recycle) computed here is the
+ **actual compressor throughput**. When you go on to compute polytropic
+ head/efficiency or shaft power from measured conditions, use this actual
+ throughput — not the metered net/export flow. Using net flow while the recycle is
+ open understates suction volume and power and mis-locates the operating point on
+ the surge map (a common error when diagnosing compressor degradation at
+ turndown).
+
+ In Python these classes are reachable through the `neqsim` package (for example
+ `from neqsim import jneqsim`).
+
+ ## References
+
+ - NeqSim: https://github.com/equinor/neqsim
+ - NeqSim Community Skills: https://github.com/equinor/neqsim-community-skills
+ - API Standard 617 — Axial and Centrifugal Compressors.
+ - API Standard 692 — Surge Control for Centrifugal Compressors.